Functions
5.17 Defrost
During heat pump operation on air/water units, the outdoor coil works as an evaporator. If the outside temperature is low, frost
may form on the coil, resulting in reduced unit effi
ciency. To free the coil from frost and restore maximum effi
ciency, μChiller
activates the defrost function. Activation depends on the value read by the reference probe (pressure transducer, low pressure
side -> evaporation temperature in the graph), on the activation threshold being exceeded, and a possible delay.
User
C
ode
Description
Def
Min
Max
U
O
M
S
S039
Defrost: start temperature
-1.0
-99.9
99.0
°C
S
S040
Defrost: reset start defrost delay threshold
1.0
S039
99.9
°C
S
S041
Defrost: delay at start-up
30
0
999
min
S
S042
Defrost: end temperature
52.0
-999.9
999.9
°C
S
S046
Defrost: min duration
1
0
99
min
S
S047
Defrost: max duration
5
0
99
min
Example of defrost activation:
300053_069_R01
D1
Set Thrs
Res Thrs
End Thrs
Te (°C)
Start
Evap
Cond
End
t (s)
Key
T
Temperature
End Thrs
End defrost temperature
Res Thrs
Reset start defrost delay threshold
Set Thrs
Start defrost temperature
D1
Defrost start delay
Start
Start defrost
End
End defrost
T_Cond
Condensing temperature
T_Evap
Evaporation temperature
Fig. 5.aa
If the defrost temperature does not exceed the reset threshold during the defrost start delay, then the defrost starts. It ends
when the reference probe (pressure transducer, high pressure side -> condensing temperature in the graph) exceeds the end
defrost temperature or the maximum defrost duration has elapsed.
Note:
for optimal defrost management, it is recommended to set the start defrost temperature to the evaporation tempe-
rature value at which ice starts forming on the coil (-1.0°C / -1.5°C); the defrost start delay expresses the time needed to accumu-
late a layer of ice that requires defrosting (30- 60 minutes). Also see the paragraph “Sliding defrost”.
5.17.1 Defrost procedure
Notes:
in the following description:
• "case with compressor ON" indicates that the phase is only featured if defrost is set with the compressor On;
• "case with compressor off " indicates that the phase is only featured if defrost is set with the compressor Off ;
End defrost can be managed in two ways:
• with the compressor off : the thermal inertia of the condenser is used to end the defrost;
• with the compressor on: to make the defrost as fast as possible.
User
C
ode
Description
Def
Min
Max
U
O
M
M
S055
Compressor after defrost 0/1=On/Off
0
0
1
-
Compressor off at end defrost
Compressor on for the entire defrost
300053_070_R01
EEV
t (s)
Fan
CP
4WV
Defrost
1
3
5
7
9
10
4
2
300053_071_R01
EEV
t (s)
Fan
CP
4WV
Defrost
1
3
5
6 7
8
4
2
Fig. 5.ab
Fig. 5.ac
Key
Defrost
Defrost request
4WV
Cycle reversal (4-way valve)
CP
Compressor capacity
Fan
Enable fans
EEV
Electronic expansion valve