95
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Supervisor table
Index
S
ize
Ref.
Type
Min/Max
R/W
UoM
Description
153
1
C000
INT
0 to 999
R/W
h
C000 - Maintenance hours threshold comp.1 circ.1 (x100)
154
1
C002
INT
0..2
R/W
C002 - Comp. 1 circ. 1 manual mode (0 = AUTO, 1 = OFF, 2 = ON)
155
1
C003
INT
0 to 999
R/W
h
C003 - Maintenance hours threshold comp. 2 circ. 1 (x100)
156
1
C005
INT
0..2
R/W
C005 - Comp. 2 circ. 1 manual mode (0 = AUTO, 1 = OFF, 2 = ON)
157
1
C006
INT
0 to 999
R/W
h
C006 - Maintenance hours comp. 1 circ. 2 (x100)
158
1
C008
INT
0..2
R/W
C008 - Comp. 1 circ. 2 manual mode (0 = AUTO, 1 = OFF, 2 = ON)
159
1
C009
INT
0 to 999
R/W
h
C009 - Maintenance hours threshold comp. 2 circ. 2 (x100)
160
1
C011
INT
0..2
R/W
C011 - Comp. 2 circ. 2 manual mode (0 = AUTO, 1 = OFF, 2 = ON)
162
1
C012
INT
30 to 999
R/W
s
C012 - Minimum compressor ON time
163
1
C013
INT
30 to 999
R/W
s
C013 - Minimum compressor OFF time
164
1
C014
INT
300 to 999
R/W
s
C014 - Minimum time between same compressor ON
165
1
C015
INT
10 to 999
R/W
s
C015 - Compressor load up time
166
1
C016
INT
5 to 999
R/W
s
C016 - Compressor load down time
167
1
S021
INT
0..23
R/W
h
Time band hours
168
1
C020
INT
5 to 999
R/W
min
C020 - Max circuit destabilisation time with one or more comp. OFF
169
1
C021
INT
0..1
R/W
C021 - Circuit capacity distribution
(0 = balanced, 1 = grouped)
170
2
C022
REAL
-99.9..99.9
R/W
K/R
C022 - Discharge temp. probe off set circ. 1
172
2
C023
REAL
-99.9..99.9
R/W
K/R
C023 - Suction temp. probe off set circ. 1
174
2
C024
REAL
-99.9..99.9
R/W
K/R
C024 - Discharge temp. probe off set circ. 2
176
2
C025
REAL
-99.9..99.9
R/W
K/R
C025 - Suction temp. probe off set circ. 2
178
2
C026
REAL
-99.9..99.9
R/W
bar/psi
C026 - Discharge pressure probe off set circ. 1
180
2
C027
REAL
-99.9..99.9
R/W
bar/psi
C027 - Suction pressure probe off set circ. 1
182
2
C028
REAL
-99.9..99.9
R/W
K/R
C028 - Condensing temp. probe off set circ. 1
184
2
C029
REAL
-99.9..99.9
R/W
K/R
C029 - Evaporation temp. probe off set circ. 1
186
2
C030
REAL
-99.9..99.9
R/W
bar/psi
C030 - Discharge pressure probe off set circ. 2
188
2
C031
REAL
-99.9..99.9
R/W
bar/psi
C031 - Suction pressure probe off set circ. 2
190
2
C032
REAL
-99.9..99.9
R/W
K/R
C032 - Cond. temp. probe off set circ. 2
192
2
C033
REAL
-99.9..99.9
R/W
K/R
C033 - Evaporation temp. probe off set circ. 2
194
1
C037
INT
0..1
R/W
C037 – Suction pressure: probe type (0 = 0-5V, 1 = 4-20mA)
195
2
C038
REAL
-1.0..99.9
R/W
bar/psi
C038 - Suction pressure: minimum probe value
197
2
C039
REAL
0.0..99.9
R/W
bar/psi
C039 - Suction pressure: max probe value
199
1
C040
INT
0..1
R/W
C040 – Discharge pressure: probe type (0 = 0-5V, 1 = 4-20mA)
200
2
C041
REAL
-1.0..99.9
R/W
bar/psi
C041 - Discharge pressure: minimum probe value
202
2
C042
REAL
0.0..99.9
R/W
bar/psi
C042 - Discharge pressure: max probe value
204
1
C043
INT
0..1
R/W
C043 - Discharge temp.: probe type (0 = NTC, 1 = NTC-HT)
206
1
C046
INT
1..2
R/W
C046 - Number of circuits on the unit
207
1
C047
INT
0..1/3
R/W
C047 - Type of compressors used
(0 = 1 ON / OFF, 1 = 2 ON / OFF, 2 = BLDC, 3 = BLDC + ON / OFF)
208
1
C048
INT
1..2
R/W
C048 - Compressor rotation type (1 = FIFO, 2 = TIME)
209
1
S000
INT
0 to 999
R/W
h
S000 - Source pump 1 maintenance hour threshold (x100)
210
1
S002
INT
0..2
R/W
S002 - Source pump 1 manual mode (0 = AUTO, 1 = OFF, 2 = ON)
212
1
S022
INT
0..59
R/W
min
Time band minutes
214
1
S008
INT
0 to 999
R/W
h
S008 - Source fan 1 circ. 1 maintenance hours threshold (x100)
215
1
S010
INT
0..2
R/W
S010 - ON/OFF source fan circ. 1 manual mode (0 = AUTO, 1 = OFF, 2 = ON)
216
1
S011
INT
0..101
R/W
%
S011 - Inverter source fan circ. 1 manual mode (0 = AUTO, 1 = 0%, 2 = 1%, .. 101 =
100%)
217
1
S012
INT
0 to 999
R/W
h
S012 - Source fan 1 circ. 2 maintenance hours threshold (x100)
218
1
S014
INT
0..2
R/W
S014 - ON/OFF source fan circ. 2 manual mode (0 = AUTO, 1 = OFF, 2 = ON)
219
1
S015
INT
0..101
R/W
%
S015 - Inverter source fan circ. 2 manual mode (0 = AUTO, 1 = 0%, 2 = 1%, .. 101 =
100%)
220
2
S016
REAL
-999.9..999.9
R/W
°C/°F
S016 - Source fan temp. threshold for cold climates
222
2
S017
REAL
0..100
R/W
%
S017 - Minimum source fan speed for cold climates
224
2
S018
REAL
0..100
R/W
%
S018 - Source fan acceleration speed for cold climates
226
1
S019
INT
0..300
R/W
s
S019 - Source fan acceleration time for cold climates
227
2
REAL
R/W
%
FC_PrwReq - Free cooling control ramp
229
2
Sprb
REAL
R
°C/°F
SPrb - Source outside air temperature;
231
2
S025
REAL
0..999.9
R/W
°C/°F
S025 - Source fan low noise set point in cooling
233
1
S026
INT
0 to 999
R/W
s
S026 - Comp. ON delay from source pump ON
234
1
S027
INT
0 to 999
R/W
s
S027 - Source pump OFF delay from comp. OFF
235
2
S028
REAL
-999.9..999.9
R/W
°C/°F
S028 - Source fan set point in cooling
237
2
S029
REAL
0..99.9
R/W
°C/°F
S029 - Source fan set point in heating
241
2
S031
REAL
0..999.9
R/W
°C/°F
S031 - Source fan set point in cooling at start-up
243
1
S032
INT
0 to 999
R/W
s
S032 - Source fan start delay in cooling
246
2
S034
REAL
0..99.9
R/W
K/R
S034 - Source fan diff erential in cooling
248
2
S035
REAL
0..99.9
R/W
K/R
S035 - Source fan diff erential in heating
250
2
S036
REAL
0..100
R/W
%
S036 - Source fan inverter min speed
252
2
S037
REAL
0..100
R/W
%
S037 - Source fan inverter max speed
254
2
S039
REAL
-99.9..99.9
R/W
°C/°F
S039 – Start defrost threshold
256
2
S040
REAL
S039..99.9
R/W
°C/°F
S040 - Reset start defrost threshold
258
1
S041
INT
0 to 999
R/W
min
S041 - Start defrost delay
259
2
S042
REAL
-999.9..999.9
R/W
°C/°F
S042 - End defrost threshold
261
1
S044
INT
0 to 999
R/W
s
S044 - Start defrost delay before 4-way valve is activated
262
1
S045
INT
0 to 999
R/W
s
S045 - End defrost delay after 4-way valve has been activated
263
1
S046
INT
0..99
R/W
min
S046 - Minimum defrost duration
264
1
S047
INT
0..99
R/W
min
S047 - Max defrost duration
Summary of Contents for uChiller UCHBD00001230
Page 2: ......
Page 4: ......
Page 6: ......
Page 105: ...105 ENG chiller 0300053EN rel 2 2 14 12 2021 Release notes Notes...
Page 106: ...106 ENG chiller 0300053EN rel 2 2 14 12 2021 Notes...
Page 107: ......