84
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Parameter table
User
Display
C
ode
Description
Def.
Min.
Max.
U
O
M
R/W
Modbus
S
U056
User side delivery temp. probe: off set
0.0
-99.9
99.9
K/R
R/W
HR083 (2R)
S
U057
Remote alarm: input logic - 0/1=NC/NO
0
0
1
-
R/W
CS008
S
U058
Cooling/heating input: logic - 0/1=NO/NC
1
0
1
-
R/W
CS009
S
x
U059
Remote ON/OFF: input logic - 0/1=NO/NC
1
0
1
-
R/W
CS010
S
U060
User pump fl ow switch: input logic - 0/1=NO/NC
0
0
1
-
R/W
CS011
S
U061
User pump overload protector: input logic
0/1=NO/NC
0
0
1
-
R/W
CS012
S
U062
2nd set point: input logic - 0/1=NO/NC
1
0
1
-
R/W
CS013
M
U063
User pump: output logic - 0/1=NO/NC
0
0
1
-
R/W
CS014
S
U064
Global alarm relay: output logic - 0/1=NO/NC
0
0
1
-
R/W
CS015
S
U065
Free cooling valve: output logic - 0/1=NO/NC
0
0
1
-
R/W
CS016
M
U066
Frost protection heater: output logic - 0/1=NO/NC
0
0
1
-
R/W
CS017
S
U067
Alarm relay confi guration - 0/1=Control alarms/All
0
0
1
-
R/W
CS018
S
U068
Free cooling: enable - 0/1=no/yes
0
0
1
-
R/W
CS019
S
U069
Free cooling: activation diff erential
3.0
0.0
99.9
K/R
R/W
HR085 (2R)
S
U070
Free cooling: hysteresis
1.5
0.0
99.9
K/R
R/W
HR087 (2R)
S
U071
Design free cooling delta T
8.0
0.0
99.9
K/R
R/W
HR089 (2R)
S
U072
Water free cooling: valve closing threshold
5.0
-999.9
999.9
°C/°F
R/W
HR091 (2R)
S
U073
Water free cooling: valve closing diff erential
3.0
0.0
99.9
K/R
R/W
HR093 (2R)
M
U074
Free cooling type
0=Air - 1=Remote coil - 2=Water
0
0
2
-
R/W
HR095
S
U075
Frost protection type
0=Heater - 1=Pump - 2=Heater/Pump
2
0
2
-
R/W
HR096
M
U076
Number of user pumps
1
1
2
-
R/W
HR097
M
U077
Type of unit
0= CH; 1= HP; 2= CH/HP
3= Condensing unit CH
4= Condensing unit CH/HP
0
0
4
-
R/W
HR098
S
U078
Unit pump in standby: enable On-Off cycles
0/1=No/Yes
0
0
1
-
R/W
CS080
S
U079
Unit pump in standby: On time
3
1
15
min
R/W
HR709
S
U080
Unit pump in standby: Off time
15
3
99
min
R/W
HR710
S
U081
Pressure alarm reset confi guration
7
0
7
-
R/W
HR239
M
U082
Frost protection type
0 = Evaporation temperature
1 = Water delivery temperature
0
0
1
-
R/W
CS093
M
U083
Type of automatic changeover
0: disabled
1: on outside temperature
2: on air return temp. (for legacy AA units only)
3: on delivery water temp. (AW and WW units only)
0
0
3
-
R/W
HR6
M
U084
Automatic changeover threshold (type 1 only (U083 =
1))
23
-99.9
99.9
°C/°F
R/W
HR765
U085
Automatic changeover dead band
2
0
99.9
K/R
R/W
HR772
U086
Automatic changeover set point lower limit
0
-99.9
999.9
°C/°F
R/W
HR774
U087
Automatic changeover set point upper limit
80
-99.9
999.9
°C/°F
R/W
HR776
U088
Frost protection heater position
0 = user
1 = source (WW units only)
2 = user and source (WW units only)
0
0
2
-
R/W
HR769
Tab. 6.a
6.2
C
ompressor
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W
Modbus
CMP = Compressor
S
C000
Comp. 1 circuit 1: maintenance hour threshold(x100)
99
0
999
h
R/W
HR153
S
C001
Comp. 1 circuit 1: reset hour counter
0
0
1
-
R/W
CS023
S
x
C002
Comp. 1 circuit 1: operating mode
-0=AUTO - 1=OFF - 2=ON
0
0
2
-
R/W
HR154
S
C003
Comp. 2 circuit 1: maintenance hour threshold(x100)
99
0
999
h
R/W
HR155
S
C004
Comp. 2 circuit 1: reset hour counter
0
0
1
-
R/W
CS024
S
x
C005
Comp. 1 circuit 2: operating mode
0=AUTO - 1=OFF - 2=ON
0
0
2
-
R/W
HR156
S
C006
Comp. 1 circuit 2: maintenance hour threshold(x100)
99
0
999
h
R/W
HR157
S
C007
Comp. 2 circuit 1: reset hour counter
0
0
1
-
R/W
CS025
S
x
C008
Comp. 2 circuit 1: operating mode
0=AUTO - 1=OFF - 2=ON
0
0
2
-
R/W
HR158
S
C009
Comp. 2 circuit 2: maintenance hour threshold(x100)
99
0
999
h
R/W
HR159
S
C010
Comp. 2 circuit 2: reset hour counter
0
0
1
-
R/W
CS026
S
x
C011
Comp. 2 circuit 2: operating mode
0=AUTO - 1=OFF - 2=ON
0
0
2
-
R/W
HR160
M
C012
Min compressor on time
180
30
999
s
R/W
HR162