μc0300053EN rel. 2.2 - 14.12.2021
Parameter table
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W
Modbus
U
ScP2
Circuit 2: suction pressure
-
-999.9
999.9
bar/psi
R
IR030 (2R)
U
Sct1
Circuit 1: suction temperature
-
-999.9
999.9
°C/°F
R
IR014 (2R)
U
Sct2
Circuit 2: suction temperature
-
-999.9
999.9
°C/°F
R
IR018 (2R)
U
x
SetA
Current set point
-
-999.9
999.9
°C/°F
R
IR046 (2R)
U
rSPt
Remote set point
-999.9
999.9
°C/°F
IR090 (2R)
U
x
SetU
Automatic set point changeover
23
U086
U087
°C/°F
R/W
HR767 (2R)
U
Opn1
ExV circuit 1: position
-
0
9999
%
R
IR050
U
Opn2
ExV circuit 2: position
-
0
9999
%
R
IR053
U
x
SSH1
Circuit 1: suction superheat
-
-999.9
999.9
°C/°F
R
IR048 (2R)
U
x
SSH2
Circuit 2: suction superheat
-
-999.9
999.9
°C/°F
R
IR051 (2R)
S
x
Hd00
BMS: serial address
1
1
245
-
R
HR147
S
x
Hd01
BMS: baud rate
3=9600 - 4=19200 - 5=38400 - 6=57600 - 7=115200
7
3
7
-
R
HR148
S
x
Hd02
BMS: settings
0=8-NONE-1
2=8-EVEN-1
4=8-ODD-1
1=8-NONE-2
3=8-EVEN-2
5=8-ODD-2
0
0
5
-
R
HR149
S
H1C1
Comp. 1 circuit 1: hour counter
-
0
99999
h
R
IR004 (2R)
S
H1C2
Comp. 2 circuit 1: hour counter
-
0
99999
h
R
IR006 (2R)
S
H2C1
Comp. 2 circuit 1: hour counter
-
0
99999
h
R
IR008 (2R)
S
H2C2
Comp. 2 circuit 2: hour counter
-
0
99999
h
R
IR010 (2R)
S
HSP1
Source pump: hour counter
-
0
99999
h
R
IR036 (2R)
S
HuP1
User pump 1: hour counter
-
0
99999
h
R
IR000 (2R)
S
HuP2
User pump 2: hour counter
-
0
99999
h
R
IR002 (2R)
S
HFn1
Fan circuit 1: hour counter
-
0
99999
h
R
IR040 (2R)
S
HFn2
Fan circuit 2: hour counter
-
0
99999
h
R
IR042 (2R)
S
x
rps1
BLDC 1speed
-
0
999.9
rps
R
IR100 (2R)
S
x
rps2
BLDC 2 speed
-
0
999.9
rps
R
IR181 (2R)
S
x
Mc1
BLDC 1 current
-
0
99.9
A
R
IR102 (2R)
S
x
Mc2
BLDC 2 current
-
0
99.9
A
R
IR183 (2R)
S
MP1
BLDC 1 power
-
0
99.9
kW
R
IR104 (2R)
S
MP2
BLDC 2 power
-
0
99.9
kW
R
IR185 (2R)
S
Drt1
Current speed drive 1 temperature
-
0
999.9
°C/°F
R
IR106 (2R)
S
Drt2
Current speed drive 2 temperature
-
0
999.9
°C/°F
R
IR187 (2R)
S
AIHs1_1 Speed drive 1 alarm log: last
-
0
99
R
IR108
S
AIHs2_1 Speed drive 1 alarm log: second-to-last
-
0
99
R
IR109
S
AIHs3_1 Speed drive 1 alarm log: third-to-last
-
0
99
R
IR110
S
AIHs4_1 Speed drive 1 alarm log: fourth-to-last
-
0
99
R
IR111
S
AIHs1_2 Speed drive 2 alarm log: last
-
0
99
R
IR189
S
AIHs2_2 Speed drive 2 alarm log: second-to-last
-
0
99
R
IR190
S
AIHs3_2 Speed drive 2 alarm log: third-to-last
-
0
99
R
IR191
S
AIHs4_2 Speed drive 2 alarm log: fourth-to-last
-
0
99
R
IR192
Tab. 6.i
6.11
S
ettings
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W
Modbus
U
x
SEtC
Cooling set point
7.0
U006
U007
°C/°F
R/W
HR307 (2R)
U
x
SEtH
Heating set point
40.0
U008
U009
°C/°F
R/W
HR309 (2R)
U
x
0-1
Unit On-Off from keypad
0=OFF 1=ON
0
0
1
-
R/W
CS54
U
x
ModE
Cooling/heating from keypad
0=Cooling 1=Heating
0
0
1
-
R/W
CS55
-
RES
Reset alarms from BMS
0/1=No/Yes
0
0
1
-
R/W
CS56
S
x
DFr
Force defrost
0=No 1=Circuit 1 2=Circuit 2 3=Circuit 1 and 2
0
0
3
-
R/W
HR78
S
x
ClrH
Reset alarm log
0/1=No/Yes
0
0
1
-
R/W
CS59
S
x
UoM
Unit of measure
0=°C/barg 1=°F/psig
0
0
1
-
R/W
CS47
S
x
rStr
Reset factory parameters
0
0
1
-
R/W
CS45
Tab. 6.j