Supervisor table
Index
S
ize
Ref.
Type
Min/Max
R/W
UoM
Description
352
1
P011
INT
0 to 999
R/W
s
P011- Oil equalisation start-up time for solenoid valve at comp. start
353
1
P012
INT
0 to 999
R/W
s
P012 - Oil equalisation solenoid valve opening time
354
1
P013
INT
0 to 999
R/W
min
P013 - Oil equalisation solenoid valve min OFF time
355
1
P014
INT
0 to 999
R/W
min
P014 - Oil equalisation solenoid valve max OFF time
356
1
P015
INT
0 to 999
R/W
min
P015 - Max oil equalisation time for management
357
1
P019
INT
0..101
R/W
%
P019 - Compressor 1 circuit 1 manual mode (0 = AUTO, 1 = 0%, ... 101 = 100%)
358
1
P020
INT
0..101
R/W
%
P020 - Compressor 1 circuit 2 manual mode (0 = AUTO, 1 = 0%, ... 101 = 100%)
359
2
P021
REAL
R/W
kPa
P021 - Maximum delta P allowed for start-up
361
1
P022
INT
R/W
s
P022 - Maximum EVD propulsion time to equalise pressure
362
1
P023
INT
R/W
%
P023 - EVD pre-opening for pre-start to equalise the pressure
363
2
P024
REAL
R/W
rps
P024 - Start-up speed
365
2
P025
REAL
R/W
rps
P025 - Maximum custom speed (rps)
367
2
P026
REAL
R/W
rps
P026 - Minimum custom speed (rps)
369
2
P027
REAL
0..100
R/W
%
P027 - BLDC speed request threshold % for call
371
2
P028
REAL
20..100
R/W
%
P028 - BLDC speed threshold to call fi xed speed compressor
373
2
P029
REAL
20..100
R/W
%
P029 - BLDC speed threshold to switch off the fi xed speed compressor
375
2
P030
REAL
R/W
P030 - Skip frequency: set 1 [010]
377
2
P031
REAL
R/W
P031 - Skip frequency: band 1 [011]
379
1
P032
INT
R/W
P032 - Enable motor overtemperature alarm (PTC) (0 = OFF, 1 = ON) [027]
380
1
P033
INT
R/W
P033 - Motor overtemperature alarm delay [028]
382
2
S051
REAL
0..999.9
R/W
rps
S051 - BLDC defrost speed
384
2
S052
REAL
0..999.9
R/W
rps
S052 - BLDC cycle reversal speed in defrost
703
1
INT
R/W
MotTyp - Carel BLDC database ID
704
1
INT
R/W
Poles - Number of motor poles
709
1
U079
INT
1..15
R/W
min
U079 - Burst function user pump ON time
710
1
U080
INT
3..99
R/W
min
U080 - Burst function user pump OFF time
732
2
S070
REAL
-99.9..99.9
R/W
K/R
S070 - Cond. 1 frost protection temp. probe off set (S3)
734
2
S071
REAL
99.9..99.9
R/W
K/R
S071 - Cond. 2 frost protection temp. probe off set (S3 exp.)
736
2
S069
REAL
0..99.9
R/W
°C/°F
S069 - Fan-Defrost function temperature set point (0 = Function disabled)
Tab. 7.c
7.4 Input
Register
Index
S
ize
Ref.
Type
Min/Max
R/W
UoM
Description
0
2
HuP1
INT
R
h
HuP1 - User pump 1 operating hours
2
2
HuP2
INT
R
h
HuP2 - User pump 2 operating hours
4
2
H1C1
INT
R
h
H1C1 - Comp. 1 circ. 1 operating hours
6
2
H1C2
INT
R
h
H1C2 - Comp. 2 circ. 1 operating hours
8
2
H2C1
INT
R
h
H2C1 - Comp. 1 circ. 2 operating hours
10
2
H2C2
INT
R
h
H2C2 - Comp. 2 circ. 2 operating hours
12
2
dSt1
REAL
R
°C/°F
dSt1 - Discharge temp. probe circ. 1
14
2
Sct1
REAL
R
°C/°F
Sct1 - Suction temp. probe circ. 1
16
2
dSt2
REAL
R
°C/°F
dSt2 - Discharge temp. probe circ. 2
18
2
Sct2
REAL
R
°C/°F
Sct2 - Suction temp. probe circ. 2
20
2
dSP1
REAL
R
bar/psi
dSP1 - Discharge pressure probe circ. 1
22
2
ScP1
REAL
R
bar/psi
ScP1 - Suction pressure probe circ. 1
24
2
Cnd1
REAL
R
°C/°F
Cnd1 - Cond. temp. probe (or converted value from pressure probe) circ. 1
26
2
EuP1
REAL
R
°C/°F
EuP1 - Evap. temp. probe (or converted value from pressure probe) circ. 1
28
2
dSP2
REAL
R
bar/psi
dSP2 - Discharge pressure probe circ. 2
30
2
ScP2
REAL
R
bar/psi
ScP2 - Suction pressure probe circ. 2
32
2
Cnd2
REAL
R
°C/°F
Cnd2 - Cond. temp. probe (or converted value from pressure probe) circ. 2
34
2
EuP2
REAL
R
°C/°F
EuP2 - Evap. temp. probe (or converted value from pressure probe) circ. 2
36
2
HSP1
INT
R
h
HSP1 - Source pump 1 operating hours
38
1
C045
INT
R
C045 - Refrigerant type (3 = R407C, 4 = R410a, 6 = R290, 10 = R744, 22 = R32)
40
2
HFn1
INT
R
h
HFn1 - Source fan 1 circ. 1: operating hours
42
2
HFn2
INT
R
h
HFn2 - Source fan 1 circ. 2: operating hours
46
2
SEtA
REAL
R
°C/°F
SEtA - Actual set point used for temperature control
48
2
SSH1
REAL
R
K/R
SSH1 - Suction superheat for circ. 1
50
1
Opn1
INT
R
%
Opn1 - EEV opening for circ. 1
51
2
SSH2
REAL
R
K/R
SSH2 - Suction superheat for circ. 2
53
1
Opn2
INT
R
%
Opn2 - EEV opening for circ. 2
54
2
rUSr
REAL
R
°C/°F
rUSr - Return water temperature from user
56
2
dUSr
REAL
R
°C/°F
dUSr - Delivery water temperature to user.
65
2
REAL
R
%
Fan1Req - Source fan circ. 1: inverter request
67
2
REAL
R
%
Fan2Req - Source fan circ. 2: inverter request
71
1
INT
R
UnitStatus - Unit status (0 = OFF from remote DI, 1 = OFF from keypad, 2 = OFF
from scheduler, 3 = OFF from BMS, 4 = OFF from CH / HP changeover mode, 5 =
OFF from alarm, 6 = Unit defrosting, 7 = Unit on, 8 = Manual mode)
90
2
rSPt
REAL
R
°C/°F
rSPt - Remote set point
92
2
REAL
R
%
PwrReq - Capacity request
96
2
REAL
R
°C/°F
SrcSetP_Circ1 - Source fan set point circ. 1
98
2
REAL
R
°C/°F
SrcSetP_Circ2 - Source fan set point circ. 2