![Carel uChiller UCHBD00001230 User Manual Download Page 25](http://html1.mh-extra.com/html/carel/uchiller-uchbd00001230/uchiller-uchbd00001230_user-manual_2557475025.webp)
25
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Installation
Analogue inputs - Master circuit 1
Ref.
Description
Type
C
onfi guration parameters
S1
Return temperature from user
NTC
Hc31
S2
Delivery temperature to user
NTC
Hc32
S3
Not present
-
Hc00
S4
Condensing pressure
0-5V
Hc34; C040; C041; C042
S5
Evaporation pressure
0-5V
Hc35; C037; C038; C039
S6
Not present
-
Hc03; U025; U026; U027
Tab. 2.z
Analogue inputs - Slave circuit 1
Ref.
Description
Type
C
onfi guration parameters
S1
Not present
-
Hc41
S2
Not present
-
Hc42
S3
Not present
-
Hc43
S4
Condensing pressure
0-5V
Hc44; C040; C041; C042
S5
Evaporation pressure
0-5V
Hc45; C037; C038; C039
S6
Not present
-
Hc05; U025; U026; U027
Tab. 2.aa
Notice:
the discharge temperature probe is automatically assigned type NTC-HT.
Digital inputs - Master circuit 1
Ref.
Description
C
onfi guration parameters
ID1
User pump fl ow switch
Hc14; U060
ID2
Compressor 1 overload
Hc15; C035
ID3
High pressure switch
C034
ID4
Not present
Hc06; C035; U059; U058; U062; U057; U061
ID5
Not present
Hc07; C035; U059; U058; U062; U057; U061
ID6
Not present
HC08; C035; U059; U058; U062; U057; U061
Tab. 2.ab
Ingressi digitali - Slave circuito 2
Ref.
Description
C
onfi guration parameters
ID1
Pump 2 overload
Hc16; U061
ID2
Compressor 1 overload
Hc17; C035
ID3
High pressure switch
C034
ID4
Not present
Hc09; C035; U059; U058; U062; U057; U061
ID5
Remote alarm
Hc10
ID6
Not present
Hc11
Tab. 2.ac
Digital outputs - Master circuit 1
Digital outputs - Slave circuit 2
Ref.
Description
C
onfi guration param.s
Ref.
Description
C
onfi guration param.s
C-NO1
Compressor 1
Hc51; C036
C-NO1
Compressor 1
Hc61; C036
C-NO2
Compressor 2
Hc52; C036
C-NO2
Compressor 2
Hc62; C036
C-NO3
User pump 1
Hc53; U063
C-NO3
User pump 2
Hc63; U063
C-NO4
Free cooling valve (*)
Hc54; U066; S063; U065
C-NO4
Not used
Hc64
C5-NO5
Alarm
Hc55; U064
C5-NO5
Alarm
Hc65
C6-NO6
Not used
Hc56
C6-NO6
Not used
Hc66
Tab. 2.ad
Tab. 2.ae
Notice:
(*) the confi guration of the output depends on the type of unit: heat pump (reverse-cycle) => reversing valve;
Chiller with free cooling => FC valve; otherwise => Frost protection heater.
Analogue outputs - Master circuit 1
Ref.
Description
Type
C
onfi guration parameters
N
otes
Y1
Modulating/On-Off fan
0-10V
Hc71
FCS1*0/CONVONOFF
Y2
Not used
0-10V
Hc72
Tab. 2.af
Analogue outputs - Slave circuit 2
Ref.
Description
Type
C
onfi guration parameters
N
otes
Y1
Modulating/On-Off fan
0-10V
Hc81
FCS1*0/CONVONOFF
Y2
Not used
0-10V
Hc82
Tab. 2.ag