40
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Initial confi guration
3.2.6 Applica: copy confi guration
Applica includes a “Clone” feature to acquire the confi guration from one unit and replicate it “one-for-one” to other units.
Procedure:
1. open Applica on the mobile device;
2. access the controller via NFC or Bluetooth, using the “Service” or “Manufacturer” profi le credentials;
3. follow the path “Confi gurations/Clone”;
4. enter a name to describe the confi guration being saved;
5. with an NFC connection: move the device bear to the display terminal on the μChiller that the confi guration is being copied
from; once the message shows the confi guration has been acquired, this is saved to the smartphone’s memory, available via
icon 2 (see the following fi gure);
6. select the saved confi guration; (with an NFC connection) move the device near to the display terminal on the μChiller that
the same confi guration is being applied to;
7. confi rm and wait for the confi rmation message.
Notice:
with a Bluetooth connection the confi guration is saved/applied on confi rmation.
With reference to the previous fi gure, tapping the icon:
1. accesses the confi gurations saved by the user;
2. accesses the confi gurations prepared by Carel;
3. accesses the saved clones.
3.3 Unit set-up parameter list
3.3.1 Unit
parameters
Notice:
follow the order shown in the table to confi gure the Unit set-up parameters.
Par.
Description
Def. Min. Max. U
O
M
U077
Type of unit
0=CH;
1=HP;
2=CH/HP:
3=Cooling-only condensing unit;
4=Reverse-cycle condensing unit;
5=Cooling-only air/air;
6=Reverse-cycle air/air/air;
0
0
6
-
S068
Source type (0=Air, 1=Water)
0
0
1
-
U076
Number of system pumps
1
1
2
-
C046
No. of unit circuits
1 1 2 -
C047
Type of compressors used (0=1 On/Off ; 1=2 On/Off ; 2=1 BLDC; 3=1 BLDC+On/Off )
0
0
1/3
-
S065
Type of source fan (0/1=Modulating/ON-OFF)
0
0
1
-
S064
Type of source air circuit (0=Independent; 1=Common)
0
0
1
-
S072
Source pump activation
0=always on
1=On with compressors on
2=control on condensing temperature
0
0
1
-
E047
ExV driver (0=Disabled; 1=Built-in; 2=EVD Evolution)
0
0
2
-
E046
EVD Evolution: valve (1=CAREL ExV, ...) (*)
(*) see EVD Evolution manual for the complete list of selectable valves
1 1 24
-
E020
MOP in cooling: threshold
30.0
-60.0
200.0
°C
E022
MOP in heating: threshold
20.0
-60.0
200.0
°C
C017
Max high pressure threshold (HP)
65.0
0.0
999.9
°C
C018
Min low pressure threshold (LP)
0.2
-99.9
99.9
bar
U068
Free cooling: enable (0/1=no/yes)
0
0
1
-
U074
Free cooling type (0=Air; 1=Remote coil; 2=Water)
0
0
2
-