89
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Parameter table
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W Modbus
M
X
F016
Heaters active during defrost (0= No, 1=Yes)
0
0
1
-
-
-
M
X
F017
Supply fan operating mode
(0=Always ON; 1=ON by temp. control)
0
0
1
-
-
-
M
X
F018
Hot-start set point
40.0
0.0
99.9
°C
-
-
M
X
F019
Hot-keep diff erential
5.0
0.0
99.9
°K
-
-
M
X
F020
Compressor request logic from digital input
(0=NC; 1=NO)
1
0
1
-
-
-
M
X
F021
Mix delivery water temperature probe calibration
(S1 expansion)
0.0
-99.9
99.9
°K
-
-
M
X
F022
Evaporator 2 water outlet temperature probe calibration
(S2 expansion)
0.0
-99.9
99.9
°K
-
-
M
X
F023
Direct relationship between digital inputs and digital outputs
for condensing unit (0=No; 1=Yes)
0
0
1
-
-
-
M
X
F024
Manual heater 1 management (0=AUTO; 1=OFF; 2=ON)
0
0
2
-
-
-
M
X
F025
Manual heater 2 management (0=AUTO; 1=OFF; 2=ON)
0
0
2
-
-
-
M
x
F026
Compressors off at low outside
temperature (air/air)
-40.0
-40.0
99.9
°C
-
-
M
F027
Enable compressor capacity control 0/1=No/Yes
0
0
1
-
R/W
CS49
M
F028
Air heating: probe for user heater temperature control
0 = ROOM - 1 = SUPPLY
FALSE
-
-
-
R/W
CS94
Tab. 6.f
6.8
B
M
S
port
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W
Modbus
S
x
Hd00
BMS: serial address
1
1
247
-
-
HR147
S
x
Hd01
BMS: baud rate
3=9600; 4=19200; 5=38400; 6=57600; 7=115200
7
3
7
-
-
HR148
S
x
Hd02
BMS: settings
0= 8-NONE-1 - 1= 8-NONE-2 - 2= 8-EVEN-1
3= 8-EVEN-2 - 4= 8-ODD-1 - 5= 8-ODD-2
1
0
5
-
-
HR149
S
x
Hd07
BMS: supervisor database 0= 32bit 1= 16bit
0
0
1
-
-
CS48
Tab. 6.g
6.9 Password
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W
Modbus
U
He00
User password
1000
0000
9999
-
-
-
S
He01
Service password
2000
0000
9999
-
-
-
M
He02
Manufacturer password
1234
0000
9999
-
-
-
M
He03
Password for profi le 1
0001
0000
9999
-
-
-
M
He04
Password for profi le 2
0002
0000
9999
-
-
-
M
He05
Password for profi le 3
0003
0000
9999
-
-
-
M
He06
Password for profi le 4
0004
0000
9999
-
-
-
M
He07
Password for profi le 5
0005
0000
9999
-
-
-
M
He08
Password for profi le 6
0006
0000
9999
-
-
-
M
He09
Password for profi le 7
0007
0000
9999
-
-
-
Tab. 6.h
6.10 Dashboard values
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W
Modbus
U
x
AFC1
Circuit 1: source water delivery temperature
-
-999.9
999.9
°C/°F
R
IR217 (2R)
U
x
AFC2
Circuit 2: source water delivery temperature
-
-999.9
999.9
°C/°F
R
IR213 (2R)
U
x
EuP1
Circuit 1: evaporation temperature (or converted value)
-
-999.9
999.9
°C/°F
R
IR026 (2R)
U
x
EuP2
Circuit 2: evaporation temperature (or converted value)
-
-999.9
999.9
°C/°F
R
IR034 (2R)
U
dSP1
Circuit 1: condensation pressure
-
-999.9
999.9
bar/psi
R
IR020 (2R)
U
dSP2
Circuit 2: condensation pressure
-
-999.9
999.9
bar/psi
R
IR028 (2R)
U
x
dSt1
Circuit 1: discharge temperature
-
-999.9
999.9
°C/°F
R
IR012 (2R)
U
x
dSt2
Circuit 2: discharge temperature
-
-999.9
999.9
°C/°F
R
IR016 (2R)
U
x
rUSr
User: return water temperature
-
-999.9
999.9
°C/°F
R
IR054 (2R)
U
x
dUSr
User: delivery water temperature
-
-999.9
999.9
°C/°F
R
IR056 (2R)
U
x
Cnd1
Circuit 1: condensing temperature (or converted value)
-
-999.9
999.9
°C/°F
R
IR024 (2R)
U
x
Cnd2
Circuit 2: condensing temperature (or converted value)
-
-999.9
999.9
°C/°F
R
IR032 (2R)
U
Sprb
Source: outside air temperature
-999.9
999.9
°C/°F
R
HR229
U
ScP1
Circuit 1: suction pressure
-
-999.9
999.9
bar/psi
R
IR022 (2R)