117
Furnace Troubleshooting Chart
Problem
Potential Cause
Corrective Action
Furnace Does Not
Light/Stay Lit
Main gas is off
Open main gas valve.
Shut off valve closed
Open shut off valve.
ON/OFF gas valve is off
Turn ON/OFF gas valve on.
Gas pressure out of range
Adjust to proper gas pressure.
Air in gas line
Purge gas line.
Dirt in burner orifices
Clean orifices with compressed air.
Spark igniter rod out of position Relocate spark igniter rod to proper area.
No spark at igniter
Refer to
“Flame Safety Control (FSC-01)” on page 126
Defective flame safety controller
Excessive drafts
Re-direct draft away from unit.
Safety device has cut power
Check limits.
Check airflow switch and tubing at the MUA board.
Dirty flame sensor
Clean flame sensor.
Defective flame sensor
Change heating set-points to call for heat.
Defective valve
Refer to
“Gas Valves” on
.
Loose gas valve wiring
Thermostat not calling for heat Change heating set-points to call for heat.
Unit cycling on high limit
Check gas pressure. Increase airflow through furnace, if
required.
Not Enough Heat
Main gas pressure too low
Increase main gas pressure – do not exceed
14 in. wc
inlet
pressure.
Unit locked into low fire
Check wiring or modulating valve settings. Refer to
“Furnace Start-Up Summary” on page 80
.
Too much airflow
Decrease airflow if possible.
Furnace undersized
Check design conditions.
Gas controls not wired properly Refer to
“Gas Valves” on
.
Thermostat setting too low
Increase thermostat setting.
Thermostat malfunction
Check thermostat.
Too Much Heat
Defective modulating gas valve Check/replace modulating valve.
Thermostat setting too high
Decrease thermostat setting.
Unit locked into high fire
Check modulation valve settings. Refer to
.
Thermostat wired incorrectly
Check thermostat wiring.
Too much primary air
Reduce primary air.
Manifold pressure set too high
Reduce manifold pressure.
Lifting Flames or
Flashback
Dirty orifice
Check and clean orifice.
Orifice too large
Check orifice size.
Insufficient primary air
Increase primary air.
Yellow Tipping Flames Misaligned orifice
Check manifold alignment.
Insufficient primary air
Increase primary air.
Orifice too large
Check orifice size.
Floating Flames or
Flame Rollout
Manifold pressure too high
Decrease manifold pressure.
Blocked vent
Check venting system.
Misaligned orifice
Check manifold alignment.