71
NOTE: Password to enter factory settings menu is 1111. If scheduling is On, occupied and
unoccupied settings will be available for some parameters.
COND FAN CONFIG
COMP MAX FREQ
MODE
MANUAL, OA TEMP DIFF
DEFAULT: OA TEMP DIFF
OA DIFF
RANGE: 0-40°F/0-22°C
DEFAULT: 20°F/11°C
MIN/MAX SPEED
RANGE: 0-100%
DEFAULT: MIN 15%/ MAX 100%
FREQ
RANGE: MIN - MAX HZ
DEFAULT: VARIES
COOL HYST
FACTORY SETTINGS
COOLING CONFIG
MIN COOL OA TEMP
MIN COOL INTAKE TEMP
MIN TEMP
RANGE: 50-70°F/10-21°C
DEFAULT: 55°F/13°C
MIN TEMP
RANGE: 50-70°F/10-32°C
DEFAULT: 55°F/13°C
SPACE
INTAKE
RANGE: 0-10°F/0-6°C
DEFAULT: 1°F/1°C
RANGE: 0-10°F/0-6°C
DEFAULT: 3°F/2°C
REHEAT CONFIG
REHEAT MODE
OFF (DEFAULT) , RH, DP,
RH&DP
DIFFERENTIALS
SPACE
DISCHARGE
RANGE: 0-30°F/0-17°C
DEFAULT: 2°F/1°C
RANGE: 0-20°F/0-11°C
DEFAULT: 2°F/1°C
RH HYST
INTAKE
SPACE
RANGE: 0-5%/°F (C)
DEFAULT: 1%/°F (C)
RANGE: 0-5%/°F (C)
DEFAULT: 1%/°F (C)
DEW POINT ADJUST
OCC/UNOCC DP ADJ
RANGE: 0-20°F/0-10°C
DEFAULT: DISCHARGE 5°F/3°C
SPACE 10°F/6°C
LOW LOAD
ENABLE
ON/OFF
DEFAULT: OFF
REHEAT VALVE MODEL
MODEL
MTW
DEFAULT: MTW
REHEAT OPTIMIZATION
ENABLE
ON TIME
ON/OFF
DEFAULT: OFF
RANGE: 1-10 M
DEFAULT: 3 M
OFF TIME
RANGE: 1-10 M
DEFAULT: 3 M
SUPERHEAT SET POINT
SP
RANGE: 5-45°F/2-25°C
DEFAULT: 20°F/12°C
OVERHEAT TIMER
MINUTES
RANGE: 1-60 M
DEFAULT: 30 M
LOW AMBIENT COOLING
ENABLE
ON/OFF
DEFAULT: OFF
SUPPLY DUCT ADJ
ON/OFF
DEFAULT: OFF
ADJUST
RANGE: 0-10°F (0-6°C)
DEFAULT: 2°F/1°C
RH/DP INPUT MODE
RH/DP
DEFAULT: DP
ENABLE
2ND EVAP SENSOR
ENABLE
ON/OFF
DEFAULT: OFF
AUX REHEAT
ENABLE
ON/OFF
DEFAULT: OFF
DYNAMIC DP CONFIG
ENABLE
ON/OFF
DEFAULT: OFF
MIN ADJ
RANGE: (-5)-30°F/(-3)-17°C
DEFAULT: DISCHARGE 1°F/1°C
SPACE 5°F/3°C
MAX ADJ
RANGE: (-5)-30°F/(-3)-17°C
DEFAULT: DISCHARGE 5°F/3°C
SPACE 10°F/6°C
ACT TEMP
RANGE: 45-60°F/7-15°C
DEFAULT: 50°F/10°C
COND MIN/MAX
RANGE: 0-100%
DEFAULT: MIN 0%/ MAX 100%
EEV POS
RANGE: 0-100%
DEFAULT: 35%
EEV CONTROL
RANGE: 0-600 S
DEFAULT: 240 S
THRTTL DELAY
RANGE: 0-900 S
DEFAULT: 300 S
VZH044 and smaller: Range 30-200Hz.
Default 200Hz
VZH052 - VZH065: Range 50-330Hz.
Default 330Hz
VZH088 and larger: Range 50-330Hz.
Default 200Hz
When Low Ambient is configured On, the
Min Cool OA Temp settings are:
Range: (-5)-70°F/(-20)-21°C
Default: 0°F/(-17°C)