NOTE: Password to enter factory settings menu is 1111. If scheduling is On, occupied and
unoccupied settings will be available for some parameters.
FACTORY SETTINGS
UNIT OPTIONS
MONITORING SENSORS
SMOKE DETECTOR
ON/OFF
DEFAULT: OFF
FILTER MONITOR
INTAKE FIRESTAT
DSCHRG FIRESTAT
FREEZESTAT
OVERHEAT
LOW GAS SWITCH
HIGH GAS SWITCH
CO SHUTDOWN
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
OUTDOOR AIR CONFIG
OUTDOOR AIR CTRL
OFF, MANUAL, 2 POSITION, OUTDOOR AIR %,
100% OA (DEFAULT), ANALOG CONTROL, PRESSURE
RETURN AS SPACE
ON/OFF
DEFAULT: OFF
OUTDOOR AIR LIMITS
RANGE: 0-MAX OA %
DEFAULT: 0%
MIN % OCC/UNOCC
MAX % OCC/UNOCC
RANGE: MIN OA-100 %
DEFAULT: 100%
RANGE: 0-MAX OA V
DEFAULT: 0V
MIN V OCC/UNOCC
MAX V OCC/UNOCC
RANGE: MIN OA-10 V
DEFAULT: 10 V
ECONOMIZER CONFIG
OFF (DEFAULT), FIXED DRY BULB, DIFF DRY BULB,
FIXED TOTAL, DIFF TOTAL
ECONOMIZER MODE
DISABLE COOLING
AT OA
RANGE: MIN-MAX V or %
DEFAULT: MIN V or %
DAMPER PRESETS
ON/OFF
DEFAULT: OFF
ENABLE
RANGE: 0-MAX OA V
DEFAULT: 0V
OCC DAMPER PRESETS
UNOCC DAMPER PRESETS
RANGE: MIN OA-10 V
DEFAULT: 10 V
PRESET OA VALUES
ENABLE
ON/OFF
DEFAULT: OFF
EDIT OA% TABLE
EDITABLE VALUES IN 1/2 VOLT INCREMENTS
(0-10V). VOLT VALUE CORRELATES TO % VALUE.
OUTDOOR AIR DEADBAND
RANGE: 0-10°F/0-6°C
DEFAULT: 5°F/3°C
DEADBAND
ENABLE
ECONOMIZER ACT
ACT ON
COOL & BLOWER(DEFAULT)/
COOLING ONLY