56
Scheduling
To set a schedule on the HMI (
), you must first enable scheduling:
Factory Settings >
Occupied Scheduling > On
Set your sensor temperature setpoints for occupied and unoccupied schedules:
User Settings > Temp
Set Points > (Varies)
Once scheduling is enabled, and the temperature setpoints are configured, you may enter your scheduled
days and times:
User Settings > Scheduling
Figure 34 - Scheduling Screen
To adjust the settings, highlight the parameter and press
ENTER
.
• The first parameter to be highlighted will be the day. Press
UP
or
DOWN
to select the day an occupied
time schedule is required.
• Press
ENTER
to continue to set a start time. Press
UP
or
DOWN
to set start time.
• Press
ENTER
to set an end time. Press
UP
or
DOWN
to set end time.
The system will run between these days, time, and desired temperature settings. When in the
UNOCCUPIED setting, the system will run at the unoccupied temperature setting.
Fan Speed and Damper Position Presets
outlines the aux pins on Connector J11 for preset settings associated with fan speed and damper
position found in
Factory Settings > Unit Options
.
NOTE: When dehumidification is enabled (Aux 1), fan or damper preset speeds will not work.
Schedule A Default
Schedule B Default
Schedule C Default
• Monday - Friday
8:00AM to 6:00PM
• Saturday and Sunday
Unocc
• Monday - Friday
Unocc
• Saturday and Sunday
Unocc
• Monday - Friday
Unocc
• Saturday and Sunday
Unocc
Table 13 - Aux Presets
Presets
Aux 1
Aux 2
Aux 3
Normal Operation (Selected Blower Mode)
Fan Speed/Damper Position 1
X
Fan Speed/Damper Position 2
X
Fan Speed/Damper Position 3
X
X
Fan Speed/Damper Position 4
X
Fan Speed/Damper Position 5
X
X
Fan Speed/Damper Position 6
X
X
Fan Speed/Damper Position 7
X
X
X
OCCUPIED SCHEDULING
MONDAY
UP
BACK
DOWN
ENTER
8:00AM TO 6:00PM
6:00PM TO 6:00PM
A
B