75
NOTE: Password to enter factory settings menu is 1111. If scheduling is On, occupied and
unoccupied settings will be available for some parameters.
FACTORY SETTINGS
UNIT OPTIONS
BLOWER CONFIG
OCC FAN PRESETS
RANGE: 0-60Hz
DEFAULT: VARIES
UNOCC FAN PRESETS
RANGE: 0-60Hz
DEFAULT: VARIES
PRESET 0-7
PRESET 0-7
PRESET 0 = 0 Hz
PRESET 1 = 40 Hz
PRESET 2 = 50 Hz
PRESET 3 = 60 Hz
PRESET 4 = 0 Hz
PRESET 5 = 0 Hz
PRESET 6 = 0 Hz
PRESET 7 = 0 Hz
FAN PRESETS DEFAULT
PRESET 0 = 0%
PRESET 1 = 80%
PRESET 2 = 90%
PRESET 3 = 100%
PRESET 4 = 0%
PRESET 5 = 0%
PRESET 6 = 0%
PRESET 7 = 0%
PWM PRESETS DEFAULT
OCC PWM PRESETS
RANGE: 0-100%
DEFAULT: VARIES
UNOCC PWM PRESETS
RANGE: 0-100%
DEFAULT: VARIES
PRESET 0-7
PRESET 0-7
RANGE
RANGE: +/- .25” w.c. or +/- 5” w.c.
DEFAULT: +/- .25” w.c.
BLOWER PRESSURE
SENSOR RANGE
CYCLE TIME
PS HYSTERESIS
PURGE CONFIG
PURGE BUTTON
ON/OFF
DEFAULT: OFF
ENABLE
PURGE TIME
RANGE: 1-120 M
DEFAULT: 15 M
DURATION
PURGE SPEED
RANGE: MIN-MAX Hz
DEFAULT: 60 Hz
VFD
DRY MODE CONFIG
ON/OFF
DEFAULT: OFF
ENABLE
ECM
RANGE: MIN-MAX%
DEFAULT: 100%
STATIC PS KP
RANGE: 5-60 S
DEFAULT: 5 S
CYCLE
RANGE: 0.10-0.15 V
DEFAULT: 0.15 V
KP
RANGE: 15-35%
DEFAULT: 25%
HYSTERESIS