74
NOTE: Password to enter factory settings menu is 1111. If scheduling is On, occupied and
unoccupied settings will be available for some parameters.
FACTORY SETTINGS
OCCUPANCY CONFIG
SCHEDULING
OVERRIDE
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
UNIT OPTIONS
BOARD CONFIG
UNIT ADDRESS
ADDRESS
80
STARTUP TIMER
TIME
RANGE: 5-240 S
DEFAULT: 15 S
TEMP UNITS
MODE
FAHRENHEIT/CELSIUS
DEFAULT: FAHRENHEIT
HMI CONFIG
NUMBER
RANGE: 1-5
DEFAULT: 1
SCREENSAVER
AVERAGE HMI
ON/OFF
DEFAULT: OFF
ON/OFF
DEFAULT: OFF
LOCK SCREEN
ON/OFF
DEFAULT: OFF
BLOWER CONFIG
BLOWER CONTROL
120V CONTACTOR, ECP, VFD MANUAL, VFD JOG, VFD 0-10V,
VFD PRESSURE, ECM, ECM 0-10V, ECM PRESSURE
BLOWER MODE
AUTO ( DEFAULT),
INTERLOCK, MANUAL
OCC/UNOCC
AIRFLOW PROVING
CONTROL
ONBOARD, REMOTE
DEFAULT: ONBOARD
PS SET POINT
RANGE: 0.5”-0.25” w.c.
DEFAULT: 0.15” w.c.
BLOWER DELAY ENABLE
START DELAY
HEAT, COOL, BOTH, OFF
DEFAULT: OFF
STOP DELAY
HEAT, COOL, BOTH, OFF
DEFAULT: OFF
BLOWER DELAY TIME
DELAY START
RANGE: 0-120 S
DEFAULT: 90 S
DELAY STOP
RANGE: 0-120 S
DEFAULT: 90 S
DOOR INTERLOCK
ENABLE
ON/OFF
DEFAULT: OFF
BLOWER PRESETS
ENABLE
ON/OFF
DEFAULT: OFF
PWM RATE LIMITS
OCC/UNOCC MIN
RANGE: 0-MAX %
DEFAULT: 0%
OCC/UNOCC MAX
RANGE: MIN-100%
DEFAULT: 100%
VFD DIRECTION
DIRECTION
FORWARD/REVERSE
DEFAULT: FORWARD
VFD FREQ LIMITS
OCC/UNOCC MIN
RANGE: 0-MAX Hz
DEFAULT: 0Hz
RANGE: MIN-80Hz
DEFAULT: 60Hz
OCC/UNOCC MAX
SCNSVR DATE TIME
DATE/TIME,
TEMP/DATE/TIME, TEMP