CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Group L1: Point-point Communication
L1.00
①
Range: 0~1
Default: 1
Master and slave
selection
0: Master
Drive send data to other external device as master.
1: Slave
Drive receive data from other external device as slave. The received data
is valid only when the conditions listed below are satisfied.
1)Command source is communication
2) Reference source is communication
3)
L1.02
= 1
4) Receive broadcast frame
L1.01
①
Range: 0~3
Default: 0
Send data
selection of
master
It is used to set send date type of master in P2P operation.
0: Torque reference, 100% corresponds to motor rated torque(
b0.00
).
1: Running frequency, 100% corresponds to max frequency(
b0.00
).
2: Setting frequency, 100% corresponds to max frequency(
b0.00
).
3: Feedback frequency, 100% corresponds to max frequency(
b0.00
).
L1.02
①
Range: 0~1
Default: 0
Point-point
communication
enable
0: Disable
1: Enable
L1.03
①
Range: 00~11
Default: 00
Usage of data
received by slave
Unit's digit: Data usage of slave
0: As torque reference
1: As frequency reference
Ten's digit: Whether to follow the master commands
0: No
1: Yes
L1.04
Range: -9.99~10.00
Default: 1.00
Gain of received
data
It is used to set the Point-to-point receive data gain for slave.
L1.05
Range: -99.9~100.0
Default: 0.0
Zero offset of
received data
Unit: %
It is used to set the Point-to-point receive data offset for slave.
The parameter of
L1.04
and
L1.05
are used to calibrate the salve received data.
If
L1.04
is expressed by character ‘a’ and the
L1.05
is expressed by character ‘b’, the received data
is expressed by character ‘x’, the result used by slave is expressed by character ‘y’, then y=a*x+b,
the range of y is -100.00%~100.00%.