CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Eb.06
Range: 0~9999
Default: 0
Accumulative
running
time(day)
threshold
Unit: Day
This parameter is with the use of Eb.07.
The AC drive accumulative running time is made up of Eb.06 and Eb.07.
3) Suppose that
Eb.06
= 25 and
Eb.07
= 10.55,then the total accumulative
running time is 25 days 10 hours and 33 minutes.
4) The accumulative running time reached function is disabled when
simultaneously setting Eb.06 and Eb.07 to 0.
The Y terminal allocated with function NO.24 ”Accumulative running time
reached” becomes ON when accumulative running time(
A0.56
+
A0.57
)
reaches the set value(
Eb.06
+
Eb.07
).And the AC drive will act as the
thousand’s digit setting of F0.21.
Eb.07
Range: 0.00~23.99
Default: 0.00
Accumulative
running
time(hour)
threshold
Unit: h
See the parameter description of
Eb.06
.
Eb.08
Range: 0.0~100.0
Default: 0.2
Detection range
Of frequency
reached
Unit: %
If the AC drive running frequency is within the certain range of the set
frequency, the Y terminal allocated with function No.7 “Frequency
reached” becomes ON.
This parameter is used to set the range within which the output frequency
is detected to reach the set frequency. The value of this parameter is a
percentage relative to
b0.00
(Max frequency). The detection range of
frequency reached is shown in the following figure.
Figure 6- 52 Detection diagram of frequency reached
Summary of Contents for CDE500 Series
Page 8: ......
Page 28: ...CDE500 Vector Control AC Drive Chapter 2 Product Information 15 C01 C02 A B D H1 W H C03 ...
Page 282: ......