CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Setting
Function
Description
9
External STOP
terminal 2
Under any control mode(b0.11 is an arbitrary value), the configuration of
this function can make the AC drive stopped according to the stop mode.
This deceleration time is fixed for E4.05(deceleration time 4).
10
Emergency Stop
When the configuration for X terminal for this function is effective, the
AC drive will stop use the shortest possible stop time.
The current arrives to the upper limit when stop in process, the bus voltage
arrives to the voltage point for the over voltage control.
This function is used to satisfy the system is in a state of emergency
occasion, and need to quickly stop.
11
Immediate DC braking
When the configuration for X terminal for this function is effective, the
AC drive immediately into DC braking state; The AC drive resumes to
operation when the terminal is invalid, and accelerate to the setting
frequency according to the setting acceleration time.
Note:
When the motor is running under high frequency, immediately switch
into DC braking may cause the over current fault.
12
Deceleration DC
braking
When the configuration for X terminal for this function is effective, the
AC drive begin to slow down. When the output frequency is reduced to
b1.13(Stop DC braking initial frequency), start to execute stop DC brake.
13
Terminal UP
Through the X terminal configuration for this function, can achieve the
increment and decrement of specific variables.
Specific variables by C0.18(UP/DOWN adjustment of choice) decision.
Adjust the speed by C0.20(terminal UP/DOWN change rate) decision.
14
Terminal DOWN
15
UP/DOWN setting
clear (terminal,
operation panel)
Through the X terminal configuration for this function, you can clear the
adjustment of terminal UP/DOWN or keypad knob, so the settings back to
the corresponding digital set value.
16
Multi-reference
terminal 1
Through the multi speed terminal 1~4, can combined up to 16 section of
frequency selection set, please refer to table below this table. When any
X terminal selects multi speed function and effective. The frequency
source forced to multi speed.
17
Multi-reference
terminal 2
18
Multi-reference
terminal 3
19
Multi-reference
terminal 4