CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
d2.14
Range: 0.0 ~ 300.0
Default: 150.0
Preset upper
torque limit of
forward
generating
Unit: %
When d2.13 is set to 0, this parameter is used as upper torque limit when
the motor is running forward in generating mode. If the torque upper limit is
analog, pulse or communication setting, 100% of the setting corresponds
to the value of d2.14, and 100% of the value of d2.14 corresponds to the
motor rated torque.
d2.15
Range: 0 ~ 7
Default: 0
Upper torque
limit source of
reverse
generating
0: d2.10
1: AI1
2: AI2
3: AI3
4: X6/FI
5: Communication
6: MIN
(
AI1,AI2
)
7: MAX
(
AI1,AI2
)
This parameter allows user to select the desired source as upper torque to
limit the motor output torque when the motor is reverse forward in
generating mode. More information, see d2.16.
d2.16
Range: 0.0 ~ 300.0
Default: 150.0
Preset upper
torque limit of
reverse
generating
Unit: %
When d2.15 is set to 0, this parameter is used as upper torque limit when
the motor is running reverse in generating mode. If the torque upper limit
is analog, pulse or communication setting, 100% of the setting
corresponds to the value of d2.16, and 100% of the value of d2.16
corresponds to the motor rated torque.
There are four motor running modes based on directions of speed and torque. See 6-D5.
Figure 6- 24 Four motor running modes