CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Setting
Function
Description
30
Motor 1/2 swtichover
The configuration of this function can select the current load motor. When
the terminal is invalid, select the motor 1;When the terminal is valid, select
the motor 2.
31
Pulse input(enabled
only for X6/FI)
Only X6 terminal effective.When X6 selects this function, the pulse signal
can be received act as the given frequency or count.
32
Command source
switchover terminal 1
When the setting of
b0.11
(command source selection) is effective, through
the configuration of these two functions, can realize the switching between
different command source.
Such as X1 selects the “command source switching terminal 1” and X2
selects the “command source switching terminal 2”. So:
When X1 and X2 has the same state, the command source is the value
of b0.11
When the X1 is valid and X2 is invalid, the command source is the next
setpoint of b0.11
When the X1 is invalid and X2 is valid, the command source is the
previous setpoint of b0.11
The range of
b0.11
is 0~2, the next of 0 is 1, the previous of 0 is 2;the
next of 1 is 2 and the previous of 1 is 0; the next of 2 is 0, the previous of
2 is 1.
Table 6- 4 The truth table of command source switch terminals 1/2
b0.11 Setpoint
Command
source switch
terminal 2
Command
source switch
terminal 1
Actual invalid
command source
0
(
Keypad control
)
OFF
OFF
Keypad control
0
(
Keypad control
)
OFF
ON
Terminal control
0
(
Keypad control
)
ON
OFF
Communication
control
0
(
Keypad control
)
ON
ON
Keypad control
1
(
Terminal control
)
OFF
OFF
Terminal control
1
(
Terminal control
)
OFF
ON
Communication
control
1
(
Terminal control
)
ON
OFF
Keypad control
1
(
Terminal control
)
ON
ON
Terminal control
2
(
Communication
control
)
OFF
OFF
Communication
control
2
(
Communication
control
)
OFF
ON
Keypad control
2
(
Communication
control
)
ON
OFF
Terminal control
2
(
Communication
control
)
ON
ON
Communication
control
33
Command source
switchover terminal 2