CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
d5.12
①
Motor 2 no-load
current
Range: 0.01 ~ motor rated current
(
b0.08
)(
drive power <=55kW
)
Default: Model dependent
Unit: A
asynchronous motor no-load 2 current.
d5.13
①
Range: 0.000 ~ 1.000
Default: 0.400
Motor 2 weaken
flux coefficient 1
The flux coefficient corresponds to 20% of flux current.
d5.14
①
Range: 0.000 ~ 1.000
Default: 0.700
Motor 2 weaken
flux coefficient 2
The flux coefficient corresponds to 50% of flux current.
d5.15
①
Range: 0.000 ~ 1.000
Default: 1.000
Motor 2 weaken
flux coefficient 3
The flux coefficient corresponds to 80% of flux current.
d5.22
①
Range: 0 ~ 2
Default: 0
motor 2 auto tune
0: No action
1: Static auto tune
2: rotational auto tune
Group d6: Motor 2 Speed Control
The AC drive can store two groups of speed control parameters. Group d2 is for motor 1 and group
d6 is for motor 2. The defines and usage is the same as motor 1. More detail information, refer to d2.
d6.00
Range: 1 ~ 100
Default: 30
Motor 2 ASR
proportional gain
Kp1
Speed control loop proportional gain (Kp1) in low speed situation.
d6.01
Range: 0.01 ~ 10.00
Default: 0.50
Motor 2 ASR
integration time
Ti1
Unit: Sec
Speed control loop proportional integral time (Ti1) in low speed situation.
d6.02
Range: 1 ~ 100
Default: 20
Motor 2 ASR
proportional gain
Kp2
Speed control loop proportional gain (Kp2) in high speed situation.
d6.03
Range: 0.01 ~ 10.00
Default: 1.00
Motor 2 ASR
integration time
Ti2
Unit: Sec
Speed control loop proportional integral time (Ti2) in high speed situation.
Summary of Contents for CDE500 Series
Page 8: ......
Page 28: ...CDE500 Vector Control AC Drive Chapter 2 Product Information 15 C01 C02 A B D H1 W H C03 ...
Page 282: ......