CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Group C0: Digital Input
C0.00
Range: 0.000~1.000
Default value: 0.010
X terminals filter
time
Unit: Sec
X1~X10
(
X6/FI act as common terminal usage
)
sample filter time setting.
Appropriate to adjustment the filter time can increase the terminal input
signal ability of anti-interference, prevent the miss-operation; but with the
slow response time.
Figure 6- 8 Digital input filter time.
C0.01
①
Range: 0~58
Default: 3
X1 Function
Set the X1 terminal of the corresponding function, a detailed explanation
see the table below.
Table 6- 3 Functions of digit input
Setting
Function
Description
0
No function
When no function assigned to terminal, set to 0 can prevent miss-operation
1
Forward JOG(FJOG)
FJOG or RJOG through the terminal, JOG status depended on
E0.00
(JOG frequency),
E0.01
(JOG acceleration time),
E0.02
(JOG deceleration time),
E0.03
(JOG stop mode).
2
Reverse JOG(RJOG)
3
Forward RUN(FWD)
When the run source is DI(
b0.11
= 1),The run command of AC drive is
depended on these terminals. A detailed explanation of usage refer to
C0.17(Terminal command mode)
.
4
Reverse RUN(REV)
5
Three-line control
6
Run pause
When the AC drive in the process of operation, the X terminal configuration
for this function effectively, the AC drive deceleration stop, at the same time
keep the relevant operation parameters. Once the X terminal is invalid, the
AC drive resumed operation.
7
Coast to stop
When the configuration for X terminal for this function effectively, the
AC drive output immediately blockade and enter to the stop state. The stop
mode is depended to b1.10.
8
External STOP
terminal 1
When the command source is keypad(b0.11), and the configuration for this
function is effective. The AC drive will stop according to the stop mode
configuration. This is equal to keypad stop.