CDE500 Vector Control AC Drive
Chapter 5 Parameter List Table
-90-
Function
Code
Name
Range
Default
Step
Description
F0.20
Fault protection action selection 2
0000~2222
0000
1
Unit's digit:
motor underload
0: Coasting stop
1: Stop by stop mode
2: Jump to 8% motor rated frequency, resume to
setting frequency when underload is inactive.
Ten's digit:
Motor overheat
(
same as F0.19 unit's digit
)
Hundred's digit:
external fault
(
same as F0.19 unit's digit
)
Thousand's digit:
RS485 communication fault
(
same as F0.19 unit's digit
)
F0.21
Fault protection action selection 3
0000~2222
0000
1
Unit's digit:
Optional card communication fault
(
same as F0.19 unit's digit
)
Ten's digit:
PID feedback over limit
(
same as F0.19 unit's digit
)
Hundred's digit:
Accumulated power on time reached fault
(
same as F0.19 unit's digit
)
Thousand's digit:
Accumulated running time reached fault
(
same as F0.19 unit's digit
)
F0.22
Fault protection action selection 4
0000~2222
0000
1
Unit's digit:
Too large speed deviation
(
same as unit's digit
)
Ten's digit:
motor over speed
(
same as unit's digit
)
Hundred's digit:
flux postion detection failt
(
same as unit's digit
)
Thousand's digit:
UVW signals feedback fault
(
same as unit's digit
)
F0.23
Fault protection action selection 5
0000~2222
0000
1
Unit's digit:
Encoder fault
0: Coasting stop
1: Switchover to V/f, and stop by stop mode
2: Swtichover to V/f, and continue running
Ten's digit:
User-defined fault 1
(
same as unit's digit
)
Hundred's digit:
User-defined fault 2
(
same as unit's digit
)
Thousand's digit:
Multi pump interlock fault
(
same as unit's digit
)
F0.24
Frequency selection for continuing
to run upon fault
0~4
0
1
0: Current running frequency
1: Setting frequency
2: Upper limit frequency
3: Lower limit frequency
4: Backup frequency upon abnormality
F0.25
Backup frequency upon abnormality
0.0~100.0
100.0
0.1%
F0.26
Fire mode enable
0~1
0
1
0: Disabled
1: Enabled
F0.27
Fire mode frequency
0.00~b0.00
50.00
0.01Hz
F0.28
Fire mode PID setting increase
0.0~200.0
10.0
0.1%
Summary of Contents for CDE500 Series
Page 8: ......
Page 28: ...CDE500 Vector Control AC Drive Chapter 2 Product Information 15 C01 C02 A B D H1 W H C03 ...