CDE500 Vector Control AC Drive
Simple operation instruction
3.4) Set the running frequency of the AC drive (salve address is 1) to 25 Hz by writing the data to
the register 0x6400 with the communication function code 0x06.
Frame
Address
Function Code
Register Address
Register Content
Check Sum
Request
0x01
0x06
0x64
0x00
0x13
0x88
0x9B
0xAC
Response
0x01
0x06
0x64
0x00
0x13
0x88
0x9B
0xAC
Remarks:
0x1388 corresponds to 5000 in decimal, which means 50 percents as communication setting value.
When the communication setting value is used for reference frequency, the base value is
b0.00
(Max
frequency,default 50Hz).
3.5) Run the AC drive (slave address is 1) forward by writing the data to the register 0x6401 with
the communication function code 0x06.
Frame
Address
Function Code
Register Address
Register Content
Check Sum
Request
0x01
0x06
0x64
0x01
0x00
0x01
0x06
0xAC
Response
0x01
0x06
0x64
0x01
0x00
0x01
0x06
0xAC
3.6) Stop the AC drive (slave address is 1) by writing the data to the register 0x6401 with the
communication function code 0x06.
Frame
Address
Function Code
Register Address
Register Content
Check Sum
Request
0x01
0x06
0x64
0x01
0x00
0x06
0x47
0x38
Response
0x01
0x06
0x64
0x01
0x00
0x01
0x47
0x38
Remarks: 0x6401 command function
Address
Command Function
6401H
(b0.11 = 2)
0001: Forward run
0002: Reverse run
0003: Forward JOG
0004: Reverse JOG
0005: Coasting stop
0006: Deceleration stop
0007: Fault reset
Summary of Contents for CDE500 Series