CDE360 Vector Control AC Drive Chapter 6 Parameters Description
d6.04
Motor 2 Low
speed switchover
frequency
Range:
0.00 ~ switchover frequency2
(
d2.05
)
Default: 5.00
Unit: Hz
switchover frequency1
d6.05
Motor 2 High
speed switchover
frequency
Range: Switchover Frequency 1
(
d2.04
)
~ Max Frequency
(
b0.00
)
Default: 10.00
Unit: Hz
switchover frequency2
d6.06
Motor 2 ASR
integration
attribute
Range: 0 ~ 1
Default: 0
0: integral separation is invalid
1: integral separation is valid
If this parameter set to 1, integration of speed loop controller is valid only
when speed error is small. Therefore, speed overshot or oscillation can be
avoided when the Ti is small.
d6.07
Range: 50 ~ 120
Default: 100
Motor 2 Vector
control slip gain
Unit: %
Setting this parameter properly can improve system performance.
d6.08
Range: 0 ~ 1023
Default: 0
Motor 2 ASR filter
time
It need not be adjusted generally and can be increased in the case of
large speed fluctuation. In the case of motor oscillation, decrease the
value of this parameter properly.
d6.09
Range: 0 ~ 7
Default: 0
Motor 2 Upper
torque limit
Source of
forward motoring
0: d2.10
1: AI1
2: AI2
3: AI3
4: X6/FI
5: Communication
6: MIN
(
AI1,AI2
)
7: MAX
(
AI1,AI2
)
This parameter allows user to select the desired source as upper torque to
limit the motor output torque when the motor is running forward in
motoring mode. More information, see d6.10.
d6.10
Range: 0.0 ~ 200.0
Default: 150.0
Motor 2 Preset
upper torque
limit of forward
motoring
Unit: %
When d6.09 is set to 0, this parameter is used as upper torque limit when
the motor is running forward in motoring mode. If the torque upper limit is
analog, pulse or communication setting, 100% of the setting corresponds
to the value of d6.10, and 100% of the value of d6.10 corresponds to the
motor rated torque.