CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Group E3: Simple PLC
Simple PLC can complete simple combination of multi-reference.
E3.00
Range: 0~2
Default: 0
Simple PLC
running mode
Simple PLC can be either the frequency source or V/F separated voltage
source.When simple PLC is used as the frequency source, whether
parameter values of
E2.01
to
E2.16
are positive or negative determines
the running direction. If the parameter values are negative, it indicates that
the AC drive runs in reverse direction.
0: Stop after the AC drive runs one cycle
The AC drive stops after running one cycle, and will not start up until
receiving another command.
1: Keep final values after the AC drive runs one cycle
The AC drive keeps the final running frequency and direction after running
one cycle.
2: Repeat after the AC drive runs one cycle
The AC drive automatically starts another cycle after running one cycle,
and will not stop until receiving the stop command.
a1
a2
a3
a4
a5
a6
a7
f1
f2
f3
f4
f6
f7
f5
d8
f8
a8
f9
a9
f10
a10
f11
a11
f12
d12
d13
a13
f13
f14
f15
a14
a15
d15
T1
T2
T3
T4
T5
T6
T7
T8
T9 T10 T11 T12 T13 T14 T15
Figure 6- 33 Simple PLC when used as frequency source
E3.01
Range: 00~11
Default: 00
Simple PLC
retentive
selection
Unit's digit (Retentive upon power failure)
Ten's digit (Retentive upon stop)
0: No 1: Yes
PLC retentive upon power failure indicates that the AC drive memorizes the PLC running moment
and running frequency before power failure and will continue running from the memorized moment
after it is powered on again. If the unit's digit is set to 0, the AC drive restarts the PLC process after it
is powered on again.