CDE360 Vector Control AC Drive Chapter 6 Parameters Description
Note:
Parameters of d1.01~1.05 will be used when motor type is set as asynchronous motor.
Please edit parameters of d1.01~d1.05 if you got the parameters of asynchronous motor.
Parameters of d1.01~1.05 can be get from running No-load dynamic auto-tune.
After running static auto-tune, only d1.01~1.03 can be got.
Parameters of d1.01~1.05 will be refreshed to default values after changing rated motor power
or voltage.
d1.15
①
Range: 0 ~ 2
Default: 0
Auto tune
AC drive can calculate and store motor parameters automatically through
auto-tune function. To get better performance, running auto-tune before
first usage is strong recommended.
0: invalid
1: static auto-tune
It is applied to applications that the motor cannot be disconnected from
the load. Set d1.15 to 1, then press the running key, static auto-tune will
be running. d1.15 will resume to 0 after auto-tune automatically.
2: rotational auto-tune(No-load)
The motor must be disconnected from the load when running
No-load dynamic auto-tune. Set d1.15 to 2, then press the running key,
static auto-tune will be running. d1.15 will resume to 0 after auto-tune
automatically. Please set appropriate accelerating/decelerating time
(accelerating time 4, decelerating time 4), otherwise, over current or over
voltage fault may be occurred. Generally, the larger rated motor power the
longer accelerating/decelerating time is needed.
Note:
Make sure the motor is static before running auto-tune.
“TUNE”will be displayed in keypad when auto-tune is running. After
auto-
tune, “TUNE”will be disappeared.
Motor parameters will be updated after auto-tune.
There are two methods to start auto-tune:
A: After setting d1.15 to 1 or 2, send a run command.
B: Run auto-tune directly through the digital terminal which is
configured as function 54 or 55.