CDE360 Vector Control AC Drive Chapter 6 Parameters Description
-
97
-
b0.10
①
Range: 1~65535
Default: 1460
Motor rated
speed
Unit: RPM
The default value of this parameter is estimated based on the motor which
have four poles.
Please set according to the motor nameplate data.
Note:
both the VF and vector control, in order to ensure the control performance, please be sure to
follow the actual motor nameplate data set the correct values of b0.06~b0.10 parameters.
b0.11
Command
source
Range: 0~2
Default: 0
The parameter is used to select command source. Run Command
includes: start, stop, forward, reverse, JOG and so on.
0: keypad control
These keys of “RUN”, “JOG”, “STOP/RST” are used to control drive run.
If the keypad
is command source then the light of “MON” on the keypad
keep off state always.
1: I/O terminal control
System control drive run, stop, forward, reverse, forward JOG, reverse
JOG and so on by configure the X terminal functions. control mode can be
two line or three line, about detail please see the parameter of
C0.17
.
If the terminal is command source then the light of “MON” on the keypad
keep bright state always.
3: communication
PC send run command to drive by RS485 field bus.
If the terminal is command source then the light of “MON” on the keypad
keep flashing state.
Note: the command source of keypad, terminal and communication can
be switched each other by the x terminal function of number 32(the
command source switching terminal 1) and number 33(the command
source switching terminal 2).
b0.12
①
Application
setting
Range: 0~13
Default: 0
0: General
1: PID application
2: Constant pressure water supply of one AC drive with two pumps
3~13: Reserved
Code
Name
Setting value when b0.12
= 1
Setting value when b0.12
= 2
b0.03
Lower limit frequency
20.00Hz
20.00Hz
b0.11
Command source
1: I/O terminal
1: I/O terminal
b1.20
Reverse prohibition
1: Reverse disabled
1: Reverse disabled
b2.00
Main frequency source
A
5: PID
5: PID