59
Vii. gas Piping
Warning
Failure to properly pipe gas supply to boiler may
result in improper operation and damage to the
boiler or structure. always assure gas piping is
absolutely leak free and of the proper size and
type for the connected load.
an additional gas pressure regulator may be
needed. Consult gas supplier.
Warning
Size corrugated stainless steel tubing (CSST)
to ensure proper capacity and minimize flow
restrictions.
A.
Size gas piping
. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to
boiler. Maximum allowable system pressure is ½
psig. Actual point of delivery pressure may be less;
contact gas supplier for additional information.
inlet Pressure 0.5 PSi or less; 0.3 inch W.C. Pressure Drop
nominal
Pipe Size, in.
inside
Diameter, in.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
131
90
72
62
55
50
46
42
40
38
¾
0.824
273
188
151
129
114
104
95
89
83
79
1
1.049
514
353
284
243
215
195
179
167
157
148
1¼
1.380
1056
726
583
499
442
400
368
343
322
304
1½
1.610
1582
1087
873
747
662
600
552
514
482
455
2
2.067
3046
2094
1681
1439
1275
1156
1063
989
928
877
2½
2.469
4856
3337
2680
2294
2033
1842
1695
1576
1479
1397
3
3.068
8584
5900
4738
4055
3594
3256
2996
2787
2615
2470
Table 19a: Maximum Capacity of Schedule 40 Black Pipe in CFH* (natural gas) For gas Pressures
of 0.5 psig or Less
inlet Pressure 0.5 PSi or less; 0.5 inch W.C. Pressure Drop
nominal
Pipe Size, in.
inside
Diameter, in.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
172
118
95
81
72
65
60
56
52
50
¾
0.824
360
247
199
170
151
137
126
117
110
104
1
1.049
678
466
374
320
284
257
237
220
207
195
1¼
1.380
1392
957
768
657
583
528
486
452
424
400
1½
1.610
2085
1433
1151
985
873
791
728
677
635
600
2
2.067
4016
2760
2217
1897
1681
1523
1402
1304
1223
1156
2½
2.469
6401
4400
3533
3024
2680
2428
2234
2078
1950
1842
3
3.068
11316
7778
6246
5345
4738
4293
3949
3674
3447
3256
* 1 CFH of Natural Gas is approximately equal to 1 MBH; contact your gas supplier for the actual heating value of your
gas.
Minimum gas valve inlet pressure is stamped on
the rating label located in the boiler’s vestibule
compartment.
2. Maximum gas demand. Refer to the boiler’s input as
printed on its rating label. Also consider existing and
expected future gas utilization equipment (i.e. water
heater, cooking equipment).
3. Length of piping and number of fittings. Refer
to Tables 19A (natural gas) or 19B (LP gas) for
maximum capacity of Schedule 40 pipe. Table 20
lists equivalent pipe length for standard fittings.
4. Specific gravity of gas. Gas piping systems for gas
with a specific gravity of 0.60 or less can be sized
directly from Tables 19A or 19B, unless authority
having jurisdiction specifies a gravity factor be
applied. For specific gravity greater than 0.60,
apply gravity factor from Table 21. If exact specific
gravity is not shown choose next higher value.
For materials or conditions other than those listed
above, refer to
National Fuel Gas Code
, NFPA
54/ANSI Z223.1, or size system using standard
engineering methods acceptable to authority having
jurisdiction.
Summary of Contents for Apex APX399
Page 65: ...65 VIII Electrical continued Figure 43 Ladder Diagram ...
Page 66: ...66 VIII Electrical continued ...
Page 67: ...67 Figure 44 Wiring Connections Diagram VIII Electrical continued ...
Page 110: ...110 1P 3 1P 2 1P 1 XIII Repair Parts continued 1C 1D 1E ...
Page 116: ...116 XIII Repair Parts continued ...
Page 118: ...118 XIII Repair Parts continued ...
Page 129: ...129 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 130: ...130 SERVICE RECORD DATE SERVICE PERFORMED ...