BTR Controls, Inc.
PROGRAMMING
DG-Mini V7 Rev. C Standard HW manual V 1.0.2
36
T
IMERS
Description:
Auto 1
The time period after which the door will close automatically after an
Auto input has been activated and released, in seconds and tenths of
seconds.
Set to zero to disable.
Manual 1
The time period after which the door will close automatically after an
Manual input has been activated and released, in seconds and tenths of
seconds.
Set to zero to disable.
Delay to Open
The time period for which an input must be maintained before the door
initiates an opening cycle.
Set to zero to disable.
Delay to Close
A time period imposed prior to any door closing event.
Set to zero to disable.
Open Alarm
The maximum time period the door can remain in the Open position
before an Open Alarm error occurs.
Set to zero to disable.
Run Timer
A safety feature that stops door movement if the DG-Mini detects that
the door is still in motion after the Run Timer period elapses.
The Run Timer is automatically set after a Quick Setup has been
performed. The Run Timer can be manually adjusted if necessary.
The Run Timer cannot be disabled.
Input Stuck
The maximum time period that an input can be held in the “active” state
before generating an Input Stuck error.
Set to zero to disable.
Summary of Contents for DG-Mini
Page 1: ...DG Mini Rev C Standard HW manual V 1 0 0 1 DG Mini Universal Door Control ...
Page 25: ...BTR Controls Inc MENU NAVIGATION DG Mini V7 Rev C Standard HW manual V 1 0 2 25 MENU TREE ...
Page 65: ...BTR Controls Inc SPECIFICATIONS DG Mini V7 Rev C Standard HW manual V 1 0 2 65 DG Mini 1500G ...
Page 68: ...BTR Controls Inc APPENDIX DG Mini V7 Rev C Standard HW manual V 1 0 2 68 APPENDIX ...
Page 69: ...BTR Controls Inc APPENDIX DG Mini V7 Rev C Standard HW manual V 1 0 2 69 ...
Page 71: ...BTR Controls Inc APPENDIX DG Mini V7 Rev C Standard HW manual V 1 0 2 71 ...