56/83 ctrlX
SAFETY
| Device type SAFEX-C.15
R911405651, Bosch Rexroth AG, DOK-XSAFE*-SAFEX-C.1XC-IT03-EN-P, Edition 03
10.1.4
Ambient data
Tabelle 42:
Ambient data
Value 1
Value 2
Temperature
0 °C ... +50 °C during
operation
-40 °C ... 70°C Bearings
(without condensation)
Protection rating
IP 20 according to EN 60529,
IP00 connector
Climate category
3K22 according to DIN EN
60721-3-3
Pollution category
2 according to DIN EN 60664-
1:2007
Minimum, maximum relative
humidity (non-condensing)
8 % … 95 %
1 g/m³ … 29 g/m³
Mechanical resistance
Shock resistance:
EN 61800-2, IEC 60721-
3-3 Class 3M1;
19.6 m/s²
Vibration:
IEC 61131-2; 5-8.4 Hz
with an amplitude of 3.5
mm; 8.4-150 Hz with 1g
peak acceleration
Free fall (shipping package)
1 m
Max. installation height
≤
3000 m above sea level
Discharge of static electricity
ESD resistance according to EN 61000-6-7
•
Criterion: according to IEC 61000-4-2
•
Test voltage: 4 kV/8 kV Contact/Air
NOTE
Failure of the product due to contaminated air
The ambient air must be free of higher concentrations of acids, alkalis, corrosive
agents, salt, metal vapors and other electrically conductive impurities.
The devices must be installed in housings or installation spaces that
meet at least the protection class IP 54 according to DIN EN 60529.
Summary of Contents for Rexroth ctrlX SAFETY SAFEX-C.12