ctrlX SAFETY
| Device type SAFEX-C.15
55/83
DOK-XSAFE*-SAFEX-C.1XC-IT03-EN-P, Edition 03, Bosch Rexroth AG
10.1.3
Electrical data
Tabelle 41:
Electrical data
Value
Supply voltage U
L
DC 24V (-10%, +20%),
Supply Type (SELV/PELV)
Max. current consumption
(logic) U
L
Fuse U
L
SAFEX-C.15
400 mA (DC 24 V)
5 A
Max. current consumption
(outputs) U
P
SAFEX-C.15
~12 A (DC 24 V)
(4 A in the scope of cULus)
2)
XG31 (8 A max.),
XG33 (4 A max.)
Fuse U
P
12 A (4 A in the scope of
cULus)
2)
Nominal data, digital inputs
DC 24 V; type 1 according to
IEC 61131-2
Nominal data, digital outputs
PP-switching
PP/PN-switching
1)
DC 24 V; 0.5 A
DC 24 V; 2.0 A
Max. capacitive load: 320 nF
Max. inductive load: 400 mJ
Nominal data, relay outputs
Use category DC13
DC 24 V; 2 A
DC 24 V; 4 A (at 0.1Hz)
Max. permissible switching
cycles over the entire service
life: 120,000 (at 4 A; DC 24V)
Max. response time
Relay
30 ms
Current consumption
Idle
Max. 400 mA (DC 24 V)
Full load
Max. 400 mA + 12 A
(Outputs) (DC 24 V)
1) PP/PN can be parameterized as 8x PP 2.0 A
2) See
Operating permit within the scope of UL/CSA