Example:
Desired temperature value: 40 °C, desired safety controller value: 45 °C.
Possible settings for this example:
Temperature set point
Safety controller mode
Safety controller set-point
40 °C
Limit (absolute)
45 °C
Offset (relative)
5 °C
13.2.2 Setting the safety controller
Press the
Setpoint setting
icon to access the “Setpoint” setting menu from Normal display.
Press the
Back
icon to go return to Normal display from any menu.
“Setpoints” menu.
Select “Safety controller”.
“Setpoints” menu.
In the field “Mode” select the desired setting “Lim-
it” or “Offset”.
“Setpoints” menu.
Select the corresponding field “Limit” or “Off-
set” (example: “Limit”)
“Limit” entry menu.
Enter the desired safety controller setpoint and
press the
Confirm
icon.
Or