Chapter 3 Functional Safety
29
3.7
Recurrent Performance Test
The recurrent performance test is used to check the safety func-
tion to uncover possibly undetected dangerous failure. The opera-
tional capability of the measuring system has to be checked in ad-
equate intervals.
It is in the responsibility of the operator to select the type of test
and the proof test interval. The intervals are dependent on the
PFD
avg
value defined in the table and chart in the section “Safety-
Technical Data” (see also FMEDA Report).
The test has to be carried out such that the proper safety function
will be proven through interaction of all components.
This is the case when the level is controlled within the scope of a
filling. If a filling is not feasible, the measuring system has to be
triggered to respond by suitable simulation of the level or of the
physical measurement effect.
The methods and procedures used in the tests have to be named
and their degree of suitability has to be specified. The tests have
to be documented.
If the function check is negative, you have to take the entire
measuring system out of service and keep the process in a safe
state through other measures.
3.8
Safety-Technical Data
Failure rates of the electronics were determined through FMEDA
according to IEC 61508. Calculations are based on the component
failure rates according to SN 29500. All numerical values refer to
an average ambient temperature of +40°C (104°F) during the op-
erating period. Calculations are further based on the information
provided in chapter 3.4 Project Planning.
λ
sd
230 Fit safe detected failure (1 FIT = failure/10
9
h)
λ
su
536 Fit safe undetected failure
λ
dd
210 Fit dangerous detected failure
λ
du
83 Fit dangerous undetected failure
SFF
>92% Safe Failure Fraction
T
Reaction
Failure reaction time
1.5 sec
max. service life of the measuring system for the
safety function.
7 years
General data
Summary of Contents for LB4710-050
Page 2: ......
Page 4: ......
Page 8: ......
Page 32: ......
Page 33: ...Chapter 3 Functional Safety Mini Switch LB 471 33...
Page 34: ...Chapter 3 Functional Safety Mini Switch LB 471 34...
Page 35: ...Chapter 3 Functional Safety Mini Switch LB 471 35...
Page 44: ......
Page 58: ......
Page 98: ......
Page 104: ......
Page 110: ...Chapter 14 Certificates Mini Switch LB 471 110...
Page 111: ...Chapter 14 Certificates Mini Switch LB 471 111...
Page 112: ...Chapter 14 Certificates Mini Switch LB 471 112...
Page 113: ...Chapter 14 Certificates Mini Switch LB 471 113 14 2 ATEX Certificate NaI Detector...
Page 114: ...Chapter 14 Certificates Mini Switch LB 471 114...
Page 115: ...Chapter 14 Certificates Mini Switch LB 471 115...
Page 116: ...Chapter 14 Certificates Mini Switch LB 471 116...
Page 117: ...Chapter 14 Certificates Mini Switch LB 471 117 14 3 ATEX Certificate GM Detector...
Page 118: ...Chapter 14 Certificates Mini Switch LB 471 118...
Page 119: ...Chapter 14 Certificates Mini Switch LB 471 119 14 4 EC Declaration of Conformity...
Page 120: ......
Page 141: ...Mini Switch LB 471 141 Notes...
Page 142: ...Mini Switch LB 471 142 Notes...
Page 145: ......
Page 147: ......
Page 149: ......
Page 151: ......
Page 161: ......
Page 195: ......
Page 215: ......
Page 219: ......
Page 223: ...Mini Switch LB 471 78 Notes...
Page 224: ...Mini Switch LB 471 79 Notes...
Page 227: ...Mini Switch LB 471 82 Y Year 21 Z Zero count rate 8 30 32 58...