The Control panel Input lines
L5
and
L6
must be 24 hour, must NOT ACTIVATE
the Alarm Outputs (Sirens) and must COMMUNICATE (via telephone)
Low
Battery
and
Missing
Sensor events to the Installer and/or the Control Station.
The Control panel Input line
L7
must be 24 hour, must ACTIVATE the Alarm
Outputs (Sirens), and must COMMUNICATE (via telephone)
Jamming
events
to the Installer and/or the Control Station.
The Control panel Input line
L8
must be 24 hour, must ACTIVATE the Alarm
Outputs (Sirens), and/or must COMMUNICATE (via telephone)
Panic
events to
the Control Station and/or the required Emergency Service (Fire, Police, Ambu-
lance).
The Control panel Tamper line must be connected to terminal
TMP
on the
Interface. If the Control panel Tamper line is Balanced, the Balance Resistor
must be connected to terminal
TMP
on the Interface.
The Control panel must change status (from Disarmed to Armed, and vice
versa) each time the Control panel terminal
K
connects to negative; the
Use
MEM for Terminal K
option must be enabled (refer to “Use MEM for Terminal
K” in the “PROGRAMMING THE INTERFACE” section); the Interface
MEM
Input
must be connected to a Control panel Output where negative is present during
armed status.
Negative must be present on terminal
O1
on the Control panel during armed
status. In this way, the Interface will record all the alarms generated by Wireless
Sensors only when the Control panel is armed.
Negative must present on terminal
O2
on the Control panel,
for at least 3
seconds
, either when the Control panel alarm memory is deleted (Reset Alarms),
or when the Control panel is armed. In this way, deletion of all the recorded
events in the Interface Memory (Sensor Alarms, Tamper, Missing, Low Battery
and Receiver Jamming) will be done, respectively, each time the User Resets
Alarms or arms the Control panel.
A 13.8 V direct current must be present between terminals
+B
and
M
on the
Control panel.
Interface BPI Level
Using jumpers
12
and
14
select
the Interface BPI Level (refer to Table 2).
BPI Level
Jumper 12
Jumper 14
5 V
5V
K
k
12 5
_
12 V
5V
J
j
12 5
_
Table 2
Selecting the Interface BPI Level
INSTALLING VECTORBRIDGE