69
E
n
g
li
s
h
Low Battery
This Output will activate when the Sensor Battery is Low. Standby status will be
restored when all the Sensor batteries are adequately charged.
Connect this Output to a Control panel Input Zone, or to the Telephone device
Input (Telephone Dialler, Telephone Communicator, etc.) programmed to com-
municate “Low Battery on Wireless Sensors” via telephone.
Missing
This Output will activate when a sensor is “Missing”. Standby status will be
restored when all sensors are “Found”.
A Sensor will be considered Missing, when the Receiver does not receive a signal
within the programmed
Supervisory Window
(refer to “Zone Supervision” and
“Supervisory Window” in the “PROGRAMMING THE INTERFACE” section).
Connect this Output to a Control panel Input Zone or to the Telephone device
Input (Telephone Dialler, Telephone Communicator, etc.)—programmed to com-
municate “Missing Wireless Sensors” via telephone.
Jamming
This Output will activate when the Receiver detects radio noise (Jamming).
Connect this Output to a Control panel Input zone—programmed to signal Tamper
(i.e. 24 hr zone).
Arming
The operating mode of this Output depends on the status of the
Use MEM x
Ter. K
option (refer to “Use MEM for Terminal K” in the “PROGRAMMING THE
INTERFACE” section):
Ø
if the
Use MEM x Ter. K
option is DISABLED (at default), Output KA will acti-
vate for 2 seconds when Arming by Wireless Key is requested;
Ø
If the
Use MEM x Ter. K
option is ENABLED, Output KA will activate for 2 seconds
when Arming by Wireless Key is requested, and the
MEM
Input is open (floating).
Connect this Output to a Control panel Input—programmed to perform Arming
operations.
Disarming
The operating mode of this Output depends on the status of the
Use MEM. x
TER. K
option (refer to “Use MEM. for Terminal K” in the “PROGRAMMING
THE INTERFACE” section):
Ø
if the
Use MEM x Ter. K
option is DISABLED (at default), Output KD will acti-
vate for 2 seconds when Disarming by Wireless Key is requested;
Ø
If the
Use MEM x Ter. K
option is ENABLED, Output KD will activate for 2 seconds
when Disarming by Wireless Key is requested, and the
MEM
Input is open (floating).
Connect this Output to a Control panel Input—programmed to perform Disarm-
ing operations.
BAT
JAM
MIS
KA
KD
INSTALLING VECTORBRIDGE
Summary of Contents for VectorBRIDGE