Chapter 9 – RS485/Modbus RTU Communications
9-6
Address
(HEX)
Parameter Name
Unit
Read/
Write
Data Value (Hex)
0x000F
Trip information
-
R
BIT 0
:OCT1 (Over Current-1)
BIT 1
: OV (Over Voltage)
BIT 2
: EXT-A (Ext Trip)
BIT 3
: BX (E-Stop)
BIT 4
: LV (Low Voltage)
BIT 5
: Not Used
BIT 6
: GF (Ground Fault)
BIT 7
: IOHT (Inverter Overheat)
BIT 8
: ETH (Motor Overheat)
BIT 9
: OLT (Overload Trip)
BIT 10
: HW-diag
BIT 11
: Not Used
BIT 12
: OCT2 (Over Current-2)
BIT 13:
OPT Error
BIT 14:
PO (Phase Open)
BIT 15
: IOLT (Inverter Overload Trip
0x0010
Input Terminal Status
-
R
BIT 0
: M1
BIT 1
: M2
BIT 2
: M3
BIT 3
: M4
BIT
4: M5
BIT 5
: M6
BIT 6
: M7
BIT 7
: M8
0x0011
Output Terminal Status
-
R
BIT 0
: AUX1
BIT 1
: AUX2
BIT 2
: AUX3
BIT 3
: AUX4
BIT 4, 5, 6:
Not Used
BIT 7
: 3A – 3C
0x0012
V1
0 – 10V
R
0 – FFC0
0x0013
V1S
0 – 10V
R
0 – FFC0
0x0014
I
0 – 20mA
R
0 – FFC0
0x0015 RPM -
R