Chapter 6 - Parameter Description [FUN]
6-12
FUN-23: Stop Mode
This parameter sets the stopping method of the drive.
LCD
Setting Range
Description
Decel
The drive stops using the
deceleration pattern.
Dc-brake
The drive stops with DC injection
braking. The drive will output a DC
voltage when the frequency goes
below the DC injection braking
frequency during deceleration.
Free-run
(Coast to stop)
The drive stops outputting
voltage immediately when the
stop signal is commanded.
Flux brake
Faster stopping times are available
by converting some of the
regenerating energy into heat at the
motor during deceleration. Flux
Brake will stop the motor as fast as
possible without tr
i
pping the drive.
☞
Caution: When DC braking or Flux braking is
used, discretion must be used as excessive motor
heating may result if the load inertia is large, if the
braking is done frequently, if the brake current is
set too high, or if the brake time is set too long.
Stop Mode: Decel
Stop Mode: Free-run
FUN
►
Stop mode
23 Decel
Factory Default:
Decel
Output Frequency
Time
FX-CM
ON
Output Voltage
Time
Time
Stop Command
Output Frequency
Time
FX-CM
ON
Output Voltage
Time
Time
Stop Command
Summary of Contents for RSi SG Series
Page 10: ......
Page 35: ...Notes...
Page 36: ......
Page 56: ...3 1 Notes...
Page 65: ...Notes...
Page 66: ......
Page 87: ...Notes...
Page 88: ......
Page 96: ...6 8 NOTES...
Page 112: ...6 24 NOTES...
Page 148: ...6 60 NOTES...
Page 172: ......
Page 188: ...Notes...
Page 198: ...Notes...
Page 212: ...iv...
Page 217: ......