[FDT-2]
AX-CX is CLOSED when the reference frequency is in
I/O-75 [FDT Bandwidth] centered on I/O-74 [FDT
Frequency], and the output frequency reaches I/O-75
centered on I/O-74.
Detecting Condition: FDT-1 condition & (Value (Output
Freq- Freq Detection)<= Freq Detection Bandwidth (I/O-
75)/2)
AX-CX configured as ‘FDT-2’
[FDT-3]
AX-CX is CLOSED when the output frequency
reaches the band centered on the FDT frequency. The
output is OPENED when the output frequency goes
outside the FDT bandwidth centered on the FDT
frequency.
Detecting Condition: Value (Freq Detection (I/O-74)-
Output Freq)<= Freq Detection Bandwidth (I/O-75)/2
AX-CX configured as ‘FDT-3’
[FDT-4]
AX-CX is CLOSED when the output frequency
reaches the FDT frequency. The output is OPENED
when the output frequency goes below the FDT
bandwidth centered on the FDT frequency.
Detecting Condition:
During Accel: Output freq >= Freq Detection
During Decel: Output freq > (Freq Detection (I/O-74) -
Freq Detection Bandwidth (I/O-75)/2)
AX-CX configured as ‘FDT-4’
[FDT-5]
This is the inverted output of [FDT-4].
Detecting Condition:
During Accel: Output freq <= Freq Detection
During Decel: Output freq < (Freq Detection (I/O-74) -
Freq Detection Bandwidth (I/O-75)/2)
AX-CX configured as ‘FDT-5’
AX-CX
CLOSED
Output Frequency
Time
Time
I/O-75 / 2
I/O-74
AX-CX
ON
Output Frequency
Time
Time
I/O-75/ 2
ON
I/O-74
AX-CX
Output Frequency
Time
Time
I/O-75 / 2
CLOSED
I/O-74
AX-CX
Output Frequency
Time
Time
I/O-75/ 2
ON
I/O-74
ON
Summary of Contents for RSi SG Series
Page 10: ......
Page 35: ...Notes...
Page 36: ......
Page 56: ...3 1 Notes...
Page 65: ...Notes...
Page 66: ......
Page 87: ...Notes...
Page 88: ......
Page 96: ...6 8 NOTES...
Page 112: ...6 24 NOTES...
Page 148: ...6 60 NOTES...
Page 172: ......
Page 188: ...Notes...
Page 198: ...Notes...
Page 212: ...iv...
Page 217: ......