Chapter 6 - Parameter Description [I/O]
6-43
I/O-20~27: Multi-function Input Terminal ‘M1, M2,
M3’, ‘M4’, ‘M5’, ‘M6’, ‘M7’, ‘M8’ Define
The multi-function input terminals can be defined for
many different applications. The following table shows
the default settings for terminals M1 through M8.
Param
LCD display
Default
Setting
I/O-20
M1 define
SPEED-L
See the
table to the
right
I/O-21 M2
define SPEED-M
I/O-22 M3
define SPEED-H
I/O-23 M4
define Reset
I/O-24 M5
define BX
I/O-25 M6
define JOG
I/O-26 M7
define FX
I/O-27 M8
define RX
Note: BX is the Drive Disable function. When
activated (On), parameter changing is disabled.
The following table shows the various functions that
can be programmed (I/O-20 ~ I/O-27) for terminals
M1 through M8.
LCD
Setting Range
Description
Speed-L
Multi-step speed - Low
Speed-M
Multi-step speed - Mid
Speed-H
Multi-step speed - High
XCEL-L Multi-accel/decel
-
Low
XCEL-M
Multi-accel/decel - Mid
XCEL-H
Multi-accel/decel - High
Dc-brake
DC injection braking during stop
2nd
Func
Exchange to 2
nd
functions
Exchange
Exchange to commercial line
-Reserved-
Reserved for future use
Up Increase
Speed
Down Decrease
Speed
3-Wire
3 wire operation
Ext Trip
External trip
Pre-heat
Motor Pre-heat function
iTerm Clear
Used for PID control
Open-loop
Exchange between PID mode and V/F
mode
Loc / Rem
Local or Remote start control
Analog hold
Hold the analog command frequency
input signal
XCEL stop
Disable Accel and Decel
P Gain2
Used for PID P2 gain control
-Reserved-
Reserved for future use
Interlock1
Used for MMC operation
Interlock2
Interlock3
Interlock4
Speed-X
Additional Step frequency selection
Reset Reset
a
fault
BX
BX (Drive Disable)
JOG Jog
FX Forward
Run/Stop
RX Reverse
Run/Stop
Ana Change
Analog input Switch-over
Ext.PID Run
Ext PID Control On / Off
Up/Dn Clr
Clears the saved frequency when
Up/Down functions are used.
Note: If any two terminals are programmed to the
same function, the drive will display the flashing
message “Over Lap”.
I/O
►
M1 define
20 Speed-L
Factory Default:
Speed-L
I/O
►
M2 define
21 Speed-M
Factory Default:
Speed-M
I/O
►
M3 define
22 Speed-H
Factory Default:
Speed-H
Summary of Contents for RSi SG Series
Page 10: ......
Page 35: ...Notes...
Page 36: ......
Page 56: ...3 1 Notes...
Page 65: ...Notes...
Page 66: ......
Page 87: ...Notes...
Page 88: ......
Page 96: ...6 8 NOTES...
Page 112: ...6 24 NOTES...
Page 148: ...6 60 NOTES...
Page 172: ......
Page 188: ...Notes...
Page 198: ...Notes...
Page 212: ...iv...
Page 217: ......