Chapter 9 – RS485/Modbus RTU Communications
9-2
9.2
Specification
9.2.1
Performance
Specification
Item
Specification
Transmission form
Bus method, Multi-drop Link System
Applicable inverter
SG series
Connectable drives
Max 31
Transmission distance
Max. 1,200m (Within 700m Recommended)
Recommended wire
0.75mm
2
(12AWG), Shield Type Twisted-Pair Wire
9.2.2
Hardware
Specification
Item
Specification
Installation
Use C+, C-,CM terminals on control terminal block
Power supply Use Insulated power from the inverter power supply
9.2.3
Communication
Specification
Item
Specification
Communication speed
19,200/9,600/4,800/2,400/1,200 bps selectable
Communication system Half duplex system
Character system
ASCII (8 bit)
Stop bit length
1 bit
Check Sum (CRC16)
2 byte
Parity bit
None
Protocol supported
Parameter Read/Write, Monitoring parameter register/execution
Broadcasting
9.2.4
Installation
Connecting the communication line
1) Connect the Modbus-RTU communication line to the inverter’s (C+), (C-) and CM terminals of the control
terminals.
2) Connect the CM terminal among inverters for stable communication.
3) Check the connection and turn ON the inverter.
4) If the communication line is connected correctly set the communication-related parameters per the following
table:
5) Install a repeater to upgrade the communication speed or longer than 1200mm communication line is used.
Repeater is required for upgrading communication quality in the noise-high environment.
Summary of Contents for RSi SG Series
Page 10: ......
Page 35: ...Notes...
Page 36: ......
Page 56: ...3 1 Notes...
Page 65: ...Notes...
Page 66: ......
Page 87: ...Notes...
Page 88: ......
Page 96: ...6 8 NOTES...
Page 112: ...6 24 NOTES...
Page 148: ...6 60 NOTES...
Page 172: ......
Page 188: ...Notes...
Page 198: ...Notes...
Page 212: ...iv...
Page 217: ......