Chapter 6 - Parameter Description [I/O]
6-58
I/O-95: Normal Open/ Normal Closed select
The digital inputs, M1, M2, M3, M4, M5, M6, M7, and
M8 can be programmed as a NO or a NC contact. If
the terminal is programmed as NO, the input will have
to be closed to activate the programmed function. If
the terminal is programmed as NC, the input will have
to be opened to activate the function.
Input
T/M
M8 M7 M6 M5 M4 M3 M2 M1
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
0: NO
1: NC
0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1
I/O-96: Input Checking Time
This sets the amount of time the drive will wait to
confirm a valid input signal on one of the digital inputs.
I/O-97: Overheat Trip Selection
I/O-98: Motor Trip Temperature
Setting Range 0 – 255
°
C
The drive can monitor motor temperature by
connecting a motor thermistor (PTC/NTC) to terminals
NT-5G (40 HP and below) or terminals ET-CM (50 HP
and above). See Thermistor Specifications on the
following page. Motor trip temperature is set with I/O-
98. Motor temperature can be viewed at parameter
FUN-56, Motor Temperature.
Param
Bit set
Function
I/O-97
2
1
0
1
Motor overheat trip
activation 0=Off, 1=On
1 -Reserved-
1
External temperature
sensor selection
0=NTC, 1=PTC
Note: Bit 1 is not used.
Examples:
Setting I/O-97 to 001 activates the motor overheat
protection using an NTC sensor.
Setting I/O-97 to 101 activates the motor overheat
protection using a PTC sensor.
In both cases, set motor trip temperature in I/O-98.
The fault displayed when using this protection is “EXT.
OHT”, External Over Heat fault.
NOTE: Inverter Overheat protection is activated
regardless of motor temp setting condition.
NOTE: Overheat protection can be monitored by
setting one of the Aux Relays (I/O-76 ~ 79) to OH.
I/O
►
In No/NC Set
95 00000000
Factory Default:
00000000
I/O
►
In CheckTime
96 1
ms
Factory Default:
1
ms
ON (Speed-L)
Spd 0 Spd 0 Spd 0 Spd 0 Spd 7 Spd 7 Spd 7 Spd 2
BX
RX
Output
freq [Hz]
Input checking time
ON
ON (FX)
ON (Speed-H)
ON (Speed-M)
ON
checking time
checking time
I/O
►
OH Trip Sel
97
010
Factory Default:
010
I/O
►
MotTripTemp
98
110
Factory Default:
110 [
C]
Summary of Contents for RSi SG Series
Page 10: ......
Page 35: ...Notes...
Page 36: ......
Page 56: ...3 1 Notes...
Page 65: ...Notes...
Page 66: ......
Page 87: ...Notes...
Page 88: ......
Page 96: ...6 8 NOTES...
Page 112: ...6 24 NOTES...
Page 148: ...6 60 NOTES...
Page 172: ......
Page 188: ...Notes...
Page 198: ...Notes...
Page 212: ...iv...
Page 217: ......