Chapter 7 – Trouble Shooting & Maintenance
7-11
4)
Power Component Check – 350 HP ~ 400 HP
Module
Test polarity
Reading
Module
Test polarity
Reading
+
-
+
-
DC Bus
Fuses
Fuse 1
across fuse
Closed
Fuse
Indicators
Fuse 1
across indicator
Closed
Fuse 2
across fuse
Closed Fuse
2
across indicator
Closed
Fuse 3
across fuse
Closed Fuse
3
across indicator
Closed
Fuses are in parallel, visual check indicators first
SCR's
SCR1
R P2
(+)
Open
Diodes
D4
R N
(-)
Open
P2 (+)
R
Open
N (-)
R
Closed
SCR2
S P2
(+)
Open
D5
S N
(-)
Open
P2 (+)
S
Open
N (-)
S
Closed
SCR3
T P2
(+)
Open
D6
T N
(-)
Open
P2 (+)
T
Open
N (-)
T
Closed
SCR3: Measurement is D1/D2 and Pre-Charge Resistor
IGBT's
Tr1
U P2
(+)
Closed
IGBT's
Tr4
U N
(-)
Open
P2 (+)
U
Open
N (-)
U
Closed
Tr3
V P2
(+)
Closed
Tr6
V N
(-)
Open
P2 (+)
V
Open
N (-)
V
Closed
Tr5
W P2
(+)
Closed
Tr2
W N
(-) Open
P2 (+)
W
Open
N (-)
W
Closed