Chapter 6 - Parameter Description [APP]
6-78
External PID Parameters
APP-80 ~ APP-97
Param
Display
Default
Range
APP-80 Ext PI mode
0 (No)
0 (No)
1 (Yes)
APP-81
Ext Ref Sel
3 (Key-Pad)
0 (I)
1 (V1)
2 (Pulse)
3 (Key-Pad)
APP-82 Ext Ref Perc 50.00 [%]
0 – 100.00 [%]
APP-83 Ext Fbk Sel
0 (I)
0 (I)
1 (V1)
2 (Pulse)
APP-85 ExtPID Pgain 1.0 [%]
0 – 999.9 [%]
APP-86 ExtPID Itime 10.0 [sec]
0 – 32.0 [sec]
APP-87 ExtPID Dtime 0 [msec]
0 – 2000 [msec]
APP-88 ExtPID lmt-H 100.00 [%] 0 – 100.00 [%]
APP-89 ExtPID lmt-L 0 [%]
0 – 30.00 [%]
APP-90 ExtPID Scale 100.0 [%]
0 – 999.9
APP-91 Ext P2-gain
100.0 [%]
0 – 999.9
APP-92 Ext P Scale
100.0 [%]
0 – 100.0
APP-93 ExtPID F-gain 0.0 [%]
0 – 999.9 [%]
APP-95 ExtPIDOut Inv 0 (No)
0 (No)
1 (Yes)
APP-97 Ext Loop Time 100 [msec] 50 – 200 [msec]
APP–97 [Ext PID Loop Time] sets the time to
activate Ext PID controller. Set the desired value
according to system.