Chapter 6 - Parameter Description [AFN]
6-26
AFN-10 ~ AFN-16: Frequency Jump
□
□
□
These parameters allow the user the ability to lock out
certain frequencies that can cause resonance in the
driven equipment. Three different jump frequency
ranges may be set. The drive will accelerate and
decelerate through the jump frequencies, but will not
be allowed to sit at the locked out frequencies.
Frequency Jump
Note: When the reference frequency is set between
the jump frequency low/high limit, it follows the low
limit frequency, marked by “
”.
Note: If jump range 1 and range 2 are overlapped,
the lower freq. will become a low limit.
AFN
►
Jump freq
10 --- No ---
Factory Default:
No
Output Frequency
Freq. Max
Reference
Frequency
10H
20H
30H
AFN-16
AFN-15
AFN-14
AFN-13
AFN-12
AFN-11
AFN
►
jump Lo 1
11 10.00 Hz
Factory Default:
10.00 Hz
AFN
►
jump Hi 1
12 15.00 Hz
Factory Default:
15.00 Hz
AFN
►
jump Lo 3
15 30.00 Hz
Factory Default:
30.00 Hz
AFN
►
jump Hi 3
16 35.00 Hz
Factory Default:
35.00 Hz