Chapter 6 - Parameter Description [APP]
6-74
Auto Change is accomplished when the following
conditions are satisfied:
The time set in APP-67 is over.
The drive output speed (Hz.) is less than the APP-68
setting.
The difference between the Reference (Set point) and
the Feedback signal is greater than the percent set in
APP-71.
All Aux motors Off (in
AUX_EXCH
Mode
)
OR One motor is running (in
MAIN_EXCH Mode
).
When the above conditions are met, the drive stops
the running motor, and changes the motor to run by
the order set in APP-66 and then continues operation
according to the new run order. The drive starts
counting only when the auxiliary motor is running.
In MAIN_EXCH Mode, when the drive output
frequency is below Auto Change Level (APP-68), the
drive automatically stops the motor and performs an
Auto change function to operate the next motor.
Refer to the wiring example when Interlock is used
during Auto change MAIN_EXCH Mode.
Wiring Diagram for Inter-Lock Configuration
Sequence Circuit for Inter-Lock Configuration
3 Phase
Input
K1
K1.1
K2
K2.2
U V W
R S T
SG
M1
M2
120V
SG
M1/SG M2/SG
M1/main
K1
K1.1
K2
K2.1
K2.1
K1
K1
K1
K2
K2
K2
K1.1
Auto
Auto
Main
Main
RLY
RLY
M1
M2
CM
S1
S2
Summary of Contents for RSi SG Series
Page 10: ......
Page 35: ...Notes...
Page 36: ......
Page 56: ...3 1 Notes...
Page 65: ...Notes...
Page 66: ......
Page 87: ...Notes...
Page 88: ......
Page 96: ...6 8 NOTES...
Page 112: ...6 24 NOTES...
Page 148: ...6 60 NOTES...
Page 172: ......
Page 188: ...Notes...
Page 198: ...Notes...
Page 212: ...iv...
Page 217: ......