Chapter 6 – Parameter Description [APP]
6-67
APP-10: High Limit Frequency for PID Control
APP-11: Low Limit Frequency for PID Control
This is the upper limit frequency at which the output
frequency is limited during PID control.
This is the lower limit frequency at which the output
frequency is limited during PID control.
APP-12: PID Output Scale
APP-13: PID P2 Gain
APP-14: P Gain Scale
This parameter sets the scale of PID controller output.
This parameter sets the second P-Gain for PID
control.
This parameter sets the conversion scale of P-Gain
and P2-Gain.
APP-15: PID Output Inversion
Parameter APP–15 [Output inversion] sets the PID
controller’s output polarity. The output can be direct
(No) or inverted (Yes).
Note: Most applications require (No), this means
as the pressure (or process variable) rises in the
system, the speed will fall. If this parameters is set
to (Yes), the speed will increase if the pressure (or
process variable) increases.
APP-17: PID Feedback U Adjustment
This feature can be useful for fan and pumps
application. It converts the linear pattern of a
feedback sensor to the squared pattern without any
additional settings.
APP
►
PID limit-H
10 60.00 Hz
Factory Default:
60.00 Hz
APP
►
PID limit-L
11 0.50 Hz
Factory Default:
0.50 Hz
APP
►
PID Out Scale
12 100.0 %
Factory Default:
100.0 %
APP
►
PID P2-gain
13 100.0 %
Factory Default:
100.0 %
APP
►
P-gain Scale
14 100.0 %
Factory Default:
100.0 %
APP
►
PID U Fbk
17
No
Factory Default:
NO
APP
►
PID Out Inv.
15 No
Factory Default:
No
Summary of Contents for RSi SG Series
Page 10: ......
Page 35: ...Notes...
Page 36: ......
Page 56: ...3 1 Notes...
Page 65: ...Notes...
Page 66: ......
Page 87: ...Notes...
Page 88: ......
Page 96: ...6 8 NOTES...
Page 112: ...6 24 NOTES...
Page 148: ...6 60 NOTES...
Page 172: ......
Page 188: ...Notes...
Page 198: ...Notes...
Page 212: ...iv...
Page 217: ......