Configuration and Settings – 3
3–21
REVERSE OVERPOWER
NO
TRIP
TRIP
Pick up
Reverse --- Relay --- Forward
Import --- DG --- Export
Export --- Utility --- Import
FORWARD UNDERPOWER
NO
TRIP
TRIP
Pick up
FORWARD OVERPOWER
NO
TRIP
TRIP
Pick up
REVERSE UNDERPOWER
NO
TRIP
TRIP
Pick up
Reverse --- Relay --- Forward
Import --- DG --- Export
Export --- Utility --- Import
Reverse --- Relay --- Forward
Import --- DG --- Export
Export --- Utility --- Import
Reverse --- Relay --- Forward
Import --- DG --- Export
Export --- Utility --- Import
Figure 3-26
Directional Power Configurations
32 #1 & #2 Delay
– Power relays should be applied
with a time delay to prevent mis-operation during
power swing, heavy load pick up or heavy load
rejection conditions.
32 Underpower
– The 32 function must be blocked
by breaker position through auxiliary contacts when
the breaker is open.