Configuration and Settings – 3
3–11
FL
2
1
2
1
2
1
Dead V1 Hot V2
Hot V1 Dead V2
Dead V1 Dead V2
X
(25) Sync Check
Phase Angle Window: 90
Upper Voltage Limit: 100
Lower Voltage Limit: 100
Sync Check Delay:
30
Dead Voltage Limit:
10
Dead Time Delay:
30
0
o
100.0 %
70.0%
1 Cycle
0%
1 Cycle
90
o
120.0 %
100.0%
8160 Cycles
50.0%
8160 Cycles
#1
Save
Cancel
Delta Voltage: 10
1.0%
50.0%
Enable
Disable
Enable
Disable
Delta Frequency: 0.1
0.001 Hz
0.500 Hz
Dead Input Initiate
Supervised by Function 79
Phase Selection:
AB
BC
Outputs
Blocking Inputs
Figure 3-14
M-3810A IPScom
®
for Windows™ 25 Sync Check Setup Dialog Screen
Path
: Relay/Setup/Setpoints/25 Sync Check
COMMANDS
Send
Sends all entered information to the control.
Cancel
Returns you to the previous window; any changes to displayed information are lost.
Summary of Contents for Syncrocloser M-3410A
Page 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Page 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Page 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Page 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Page 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Page 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...