A–8
M-3410A Instruction Book
(46) Negative Sequence Overcurrent
Definite Time
Pickup
3 to 300%
( _______________ )
Delay
1 to 8160 Cycles
( _______________ )
Outputs
o
#2
o
#1
Blocking Inputs
o
FL
o
#2
o
#1
Inverse Time (Intertie)
Pickup
3 to 100%
( _______________ )
Time Dial
Standard Curves 1–4
0.5 to 11.0
( _______________ )
IEC Curves 5–8
0.05 to 1.10
( _______________ )
I
2
2
t=K
Max Time
600 to 65500 Cycles
( _______________ )
Curves
o
Definite Time
o
Inverse Time
o
Very Inverse
o
Extremely Inverse
o
IECI
o
IECVI
o
IECEI
o
IECLTI
o
(I square)*t = K
Outputs
o
#2
o
#1
Blocking Inputs
o
FL
o
#2
o
#1
(47) Negative Sequence Overvoltage
#1 Pickup
4.0 to 100.0%*
( _______________ )
#1 Delay
1 to 8160 Cycles
( _______________ )
#1 Outputs
o
#2
o
#1
#1 Blocking Inputs
o
FL
o
#2
o
#1
#2 Pickup
4.0 to 100.0%*
( _______________ )
#2 Delay
1 to 8160 Cycles
( _______________ )
#2 Outputs
o
#2
o
#1
#2 Blocking Inputs
o
FL
o
#2
o
#1
*(Of Nominal Voltage)
Table A-4
Relay Setpoints and Settings Record Form (page 4 of 8)
Summary of Contents for Syncrocloser M-3410A
Page 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Page 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Page 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Page 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Page 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Page 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...