Configuration and Settings – 3
3–33
IECI
IECVI
IECEI
IECLTI
Save
Cancel
Pickup:
Time Dial:
0.50 A
0.5
6.00 A
11.0
Outputs
Blocking Inputs
2
1
2
1
FL
Curves
Definite Time Inverse Time Very Inverse Extremely Inverse
#1
(51N) Inverse Time Residual Overcurrent
X
Figure 3-38
M-3810A IPScom
®
for Windows™ (51N) Inverse Time Residual
Overcurrent Setup Dialog Screen
Path
: Relay/Setup/Setpoints/51N Inverse Time Residual Overcurrent
COMMAND BUTTONS
Save
Saves all entered information to the control.
Cancel
Returns you to the previous window; any changes to displayed information are lost.
51N Inverse Time Residual Overcurrent
The Inverse Time Residual Overcurrent (3
I
0
) function
(51N) provides protection against ground faults.
Since normal residual current is usually much lower
than the full load phase current, this function can
be set more sensitively than the phase overcurrent
protection.
The setting and time delay should be coordinated
with system elements to assure desired operation.
The curves available for use are shown in Appendix
D, Inverse Time Curves, Figures D-1 through D-8.
They cover a range from 1.5 to 20 times pickup.
For currents beyond 20 times the pickup setting,
the relay operating time will remain the same as the
20 times pickup setting.
Summary of Contents for Syncrocloser M-3410A
Page 1: ...Instruction Book M 3410A Intertie Generator Protection Relay ...
Page 39: ...xiv M 3410A Instruction Book This Page Left Intentionally Blank ...
Page 71: ...M 3410A Instruction Book 2 28 This Page Left Intentionally Blank ...
Page 121: ...M 3410A Instruction Book 3 50 This Page Left Intentionally Blank ...
Page 161: ...1 3 A B C M 3410A Instruction Book 4 40 This Page Left Intentionally Blank ...
Page 223: ...M 3410A Instruction Book F 2 This Page Left Intentionally Blank ...